Floor Protection; Protection De Sol - Stuv 16-Z Mode D'emploi

Table des Matières

Publicité

4.4 Floor protection

6"
Stûv 16/58- Z
Stûv 16/68- Z
20
Stûv 16/78- Z
Floor protector's R-value
It's important to set the position of the stûv because it
gives you an idea of which material to use for the no-
combustible floor protector. The protector needs to
have an R-value equal or upper to the one in the chart.
Example:
If the Stûv is positioned 9 '' above the ground. The
R-value of the material will have to be at least 0.28!
H: Clearence /
Dégagement
H
> 11 1/2
H
11 1/2 >
> 8 1/2
H
8 1/2 >
> 6 1/2
H
6 1/2 >
> 4 1/2
H = 0
STÛV WOOD-BURNING STOVES INSTALLATION / STÛV INSTALLATION POÊLES À BOIS
Sealing strips/
Bandes d'étanchéité
Floor protector/
Dalle de protection
F
H
6"
C
C+
C
C+
23''
35''
27''
39''
Canada: 18''
31''
43''
R ≥
Ex:
0
1a
0.28
2a
1.29
3a
2.56
4a
No combustible floor /
plancher incombustible

4.4 Protection de sol

Floor protector/
Dalle de protection
Facteur R de la dalle de protection au sol
F
La distance de votre Stûv par rapport au sol est importante
pour déterminer le matériau non combustible à utiliser
U.S: 16''
pour votre dalle au sol. Celle-ci devra avoir un facteur
R égal ou supérieur aux données du tableau.
Exemple:
Si le foyer est positionné 9 ''du sol. Le facteur R de la
dalle de sol devra être de 0.28 au minimum!
Facteur R de...
1/4'' Céramique R = 0.02 ----- Ceramic*
1/2'' fibrociment R = 0.26 ---- Cement board**
1/2'' micore 160
1'' micore 160
_____________________
EXAMPLES / EXEMPLES:
1a.
Any non-combustible material
Tout matériau non-combustible
2a.
1/2'' fibrociment ** (0.26)
1/4'' céramique (0.02)
3a.
1/2'' micore 160² (1.27)
1/4'' céramique* (0.02)
4a.
1'' micore 160 (2.54)
1/4'' céramique* (0.02)
F
18
16
From the glass /
De la vitre
H
Sealing strips/
Bandes d'étanchéité
R=1.27
2
R= 2.54
2
+
= 0.28 R
+
= 1.29 R
= 2.56 R

Publicité

Table des Matières
loading

Table des Matières