AVENTICS | DDL, DDL-E | 1987765499–BDL–001–AC
Diagnostic
See chapter 8.3
Diagnosis parameters
Z is the starting
address in the
controller's
diagnosis area.
8.2 Software diagnosis
Table 12:
Bit diagnosis meanings
Byte Bit Valve unit diagnosis
Z
0
Electronics voltage
supply
1
Valve voltage supply
7
DDL communication
Z+1
0
Output 0
1
Output 1
2
Output 2
3
Output 3
4
Output 4
5
Output 5
6
Output 6
7
Output 7
Z+2
0
Output 8
...
...
7
Output 15
Z+3
0
Output 16
...
...
7
Output 23
Z+4
0
Output 24
...
...
7
Output 31
Bit
0 = no diagnosis
status
1 = Diagnosis notice
8.3 Diagnosis parameters
1 byte is available per DDL participant. Every parameter
byte can be individually set for every participant. The
parameters are not transferred cyclicly.
The DDL participants provide the DDL master with this
function. Several field bus systems (e.g. PROFIBUS DP)
present comfortable setting possibilities together with
the PLC. This is not currently available with other field bus
systems. They use default parameters instead.
< 19.2 V or
> 28.8 V
< 21.6 V or
> 26.4 V
Output short-
W
cicuited or
open (see
parameter
description)
A short circuit
W
can only be
recognized if
the output is
selected.
An open
W
output can
only be
recognized if
it is not
selected.