AVENTICS | DDL, DDL-E | 1987765499–BDL–001–AC

Presettings

Tabelle 5:
Bus coupler diagnostics display
LED
Signal
SENSOR/
green
LOGIC
POWER
SUPPLY
VALVE
green
POWER
SUPPLY
DDL
off
Error
Description
Voltage within tolerance
off
No voltage available
blink
Voltage < 19,2 V or > 28,8 V
Voltage within tolerance
off
No voltage available at sensor/logic
blink
Voltage < 21,6 V or > 26,4 V
DDL communication functioning
red
No DDL communication
(See Chapter 8.2 for software diagnosis)
5
Presettings

5.1 Setting the operating mode

The address for the bus coupler is set on switch S1.
Switch S2 is used to set:
the data length for output data
W
the baudrate
W
the connection for the DDL line.
W
Both switches are located below the PG screw cap.
Changes during operation
Changes to the DDL mode are only taken over after a
voltage reset.
Never change the settings during operation.
O
Turn the device off before changing the address
O
setting.
NOTICE