Aventics DDL Série Mode D'emploi page 51

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

POWER X10 plug
assignment (only
DDL-E bus coupler,
order number
1827030190)
1
2
AVENTICS | DDL, DDL-E | 1987765499–BDL–001–AC
Please observe the followings:
Dangerous voltages
A power pack without safe isolation may lead to
dangerous voltages in the case of a fault. This may
damage the system and cause injuries arising from
electric shock.
Only use a power pack with safe isolation
O
according to EN 60747, classification VDE 0551!
This ensures that the electric circuits comply with
SELV/PELV electric circuits in accordance with
IEC 60364-4-41.
Total current is too high
The currents from the sensor and valve line (each
max. 3 A) are summed up. If the total output of the
0 volt line is greater than 4 A, the device's plug and
conductors will be overloaded.
Design the DDL system so that the total output of
O
the 0 volt line is less than 4 A.
Table 8:
Pin
1
4
2
3
4
3
CAUTION
NOTICE
POWER X10 plug assignment on the DDL-E
bus coupler
Assignment
DDL-E bus coupler voltage supply for logics,
sensors and other DDL participants
Valve voltage supply and other DDL
participants
Grounds for voltages at pin 1 and pin 2
Functional ground
51
Installation

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ddl-e

Table des Matières