TECHNICAL DATA

MODEL
TYPE
OUTPUT
(1)
FUEL
- Net calorific value
- Absolute density
- Max. delivery
- Pressure at max. delivery
(2)
STANDARD APPLICATIONS
AMBIENT TEMPERATUR
COMBUSTION AIR TEMPERATURE
ELECTRICAL SUPPLY
ELECTRIC MOTOR
OPERATING CURRENT
START UP CURRENT
IGNITION TRANSFORMER
ELECTRICAL POWER CONSUMPTION
ELECTRICAL PROTECTION
IN CONFORMITY WITH EEC DIRECTIVES
NOISE LEVELS
(3)
APPROVAL
(1) Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(2) Pressure at test point 5)(A)p.8, with zero pressure in the combustion chambre.
(2) Sound pressure measured in manufacturers combustion laboratory, with burner operating on test boiler and at maximum rated output.
COUNTRY
IT-AT-GR-DK-FI-SE-CH-CZ-EE-
HU-IS-LT-NO-Sl-SK-TR-RO
ES-GB-IE-PT
NL
FR
DE

ACCESSORIES

(optional):
KIT FOR SIGNAL CONVERTER: 3010415
POTENTIOMETER KIT: 3013560
RMG INTERFACE KIT: 3002719
OUTPUT POWER REGULATOR KIT: Under modulating operation, the burner automatically adapts to one of an infinite number of firing rates
between the low and high flame output position, thus ensuring stable operating conditions in terms of temperature or pressure. Two components
should be ordered: • Power regulator to install to the burner; • probe to install to the boiler.
PARAMETER TO BE CHECKED
Temperature
Pressure
GAS TRAIN ACCORDING TO REGULATION EN 676 (with valves, pressure governor and filter): see page 16.
Important:
The installer is responsible for the addition of any safety device not forseen in the present manual.
kW
MAX.
Mcal/h
kW
MIN.
Mcal/h
3
kWh/Sm
3
Mcal/Sm
3
kg/Sm
3
Sm
/h
mbar
°C
°C max
V
Hz
rpm
W
V
A
A
V1 - V2
I1 - I2
W max
dBA
CE
CATEGORY
II
2H3B/P
II
2H3P
II
2L3B/P
II
2Er3P
II
2ELL3B/P
Range
- 100...+ 500°C
0...2.5 bar
0...16 bar
730
628
146
126
NATURAL GAS: G20 - G21 - G22 - G23 - G25
G20
9.45
8.2
0.68
77.2
17.5
Boilers: water, steam, diathermic oil
0 - 40
60
230 - 400 with neutral ~ +/- 10%
50 - three-phase
2800
1100
220 - 240
4.8 - 2.8
33 - 19
230 V - 2 x 5 kV
1.45 A - 50 Hz - 30 mA
1400
IP 40
90/396 - 89/336 - 2004/108 - 73/23 - 2006/95 - 92/42
75
IN PROGRESS
COUNTRY
BE
LU
LV
CY-MT
PROBE
Type
Code
PT 100
3010110
Output probe
3010213
4...20 mA
3010214
6
RX 700 S/P
854 T2
G25
8.13
7.0
0,75
89.8
23
CATEGORY
I
I
2E(R)B,
3
I
2E3B/P
I
2H
I
3B/P
POWER REGULATOR
Type
RWF40
3010414
GB
Code

Publicité