Installation (Seuls les installateurs qualifiés)
Termination Requirements
!
Venting terminals shall not be recessed into a wall or siding.
A
Minimum 9" (229mm) clearance from any door or window
B
Minimum 12" (305mm) above any grade, veranda, porch, deck or balcony
C
Minimum 1" (25mm) from outside corner walls
NOTE: Clearance in accordance with local installation codes and the requirements
of the gas supplier.
D
Minimum 1" (25mm) from inside corner walls
NOTE: Clearance in accordance with local installation codes and the requirements
of the gas supplier.
E
Minimum 11" (279mm) clearance below unventilated soffits or roof surfaces.
Minimum 18" (457mm) clearance below ventilated soffits.
Minimum 6" (152mm) clearance below roof eaves.
NOTE: Vinyl surfaces require 24" (610mm)
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
F
Minimum 12" (305mm) clearance below a veranda, porch, deck or balcony.
NOTE: Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
G
Minimum 48" (1219mm) clearance from any adjacent building.
H
Minimum 84" (2134mm) clearance above any grade when adjacent to public walkways or driveways.
NOTE: may not be used over a walkway or driveway shared by an adjacent building.
I
Minimum 9" (229mm) clearance to any non-mechanical air supply inlet to the building or the combustion air inlet
to any other appliance.
J
Minimum 36" (914mm) clearance above any mechanical air supply inlet if within 10' (3M) horizontally.
K
Minimum 36" (914mm) from the area above the meter/regulator (vent outlet) - this extends 15' (4.5M) above the regulator
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
L
Minimum 36" (914mm) from the meter/regulator (vent outlet).
NOTE: Clearance in accordance with local installation codes and the requirements of the gas supplier.
M
Minimum 12" (305mm) above the roof line (for vertical terminations).
N
Minimum 24" (610mm) horizontal clearance to any surface (such as an exterior wall) – for vertical terminations.
G
NOTE: Measure clearances to the nearest edge of the exhaust hood.
•
Use the vinyl siding standoff when installing on an exterior with vinyl siding.
•
Vent termination must not be located where it will become plugged by snow or other material
© Travis Industries
E
N
M
K
A
F
D
L
4051112
E
I
C
B
Roof
Surface
11" Min.
(279mm)
6" Min.
(152mm)
E
A
J
H
100-01271_FR
13
Roof
Eaves