7.3
Setting
8017858.1A15 / 2020-12-14 | SICK
Subject to change without notice
% of sensing range
0
–5
1
6%/90%
–10
–15
–20
0
50
100
150
(1.97)
(3.94)
(5.91)
Figure 2: HTF18L, % of sensing range
Figure 3: Description of the sensing range areas
Sensing range setting
Sensor which it is not possible to set: The sensor is adjusted and ready for operation.
Refer to graphic to check the function. If the switching output fails to behave in accor‐
dance with graphic, check application conditions. See section Fault diagnosis.
Sensor with potentiometer (without IO Link):
The sensing range is adjusted relative to the background with the potentiometer (type:
270°).
Clockwise rotation: sensing range increased; counterclockwise rotation: sensing range
reduced.
Turn the potentiometer clockwise until the yellow LED indicator lights up. When an
object is moved into the path of the beam, the yellow LED indicator must go out. If the
yellow LED indicator remains lit when an object is moved into the path of the beam,
repeat the adjustment.
Sensor with potentiometer (with IO Link):
90%/90%
3
20%/90%
2
200
250
300
(7.87)
(9.84)
(11.81)
Distance in mm (inch)
7
COMMISSIONING
17