Installing the unit in any of the following places may lead to
malfunction:
The site contains mineral oils such as cutting lubricant
Seaside where the air contains much salt.
Hot spring area where corrosive gases exist, e.g., sulfide gas.
Factories where the power voltage fluctuates seriously.
The place with direct sunlight and other heat supplies. If
there's no way to avoid these, please install a covering.
Place like kitchen where oil permeates.
Place where strong electromagnetic waves exist.
Place where flammable gases or materials exist.
Place where acid or alkali gases evaporate.
Consider sound emission
Noise levels could represent an inconvenience if installed in areas
that require extreme silence, example near bedrooms
Functional spaces
Unit
Diameter
A
If installed in inclosed space
The unit must be located in a space >15m³, and must have
unrestricted air flow.
Make sure there is enough Installation space.
For optimal efficiency and serviceability, the following clearances
should be maintained:
400mm on the air inlet side;
400mm on the air outlet side;
600mm in the back;
600mm in the front.