The AC power cables must be at least equal to or greater than the values provided in the table below (depending on the
length of the cable):
Model
12-40
12-60
The type of cable (H07-VK, MX, etc.) should be defined by the installer according to the application type and applicable
standards.
For applications where the electricity network may be either 115VAC or 230VAC, always choose the cross section
recommended for 115VAC.
Always use cable markers without insulating collars in accordance with installation standards governing AC network
input connections.
The rating of the upstream circuit-breakers should match the equipment's requirements.
Mounting of AC supply connector
The AC input must be made using a WAGO connector type WINSTA reference 770-103. (Not provided in OE version).
Minimum cross-section for
115VAC
3 x 2,5 mm²
Minimum cross-section
for 230VAC
3 x 1,5 mm²
3 x 1,5 mm²
39