W
3.2
IRING
When connecting or disconnecting a cable, the charger's power supply must be turned off and the batteries electrically
insulated from the charger.
The references for additional cables and connectors required for the appliance to operate efficiently are provided in the
following paragraphs: failure to comply with these provisions renders the warranty null and void.
3.2.1 Typical installation
Ground Fault
Circuit
Interrupter
The chargers have 3 or 4 outputs depending on the model (see 3.2.3).
3.2.2 Cable from the public AC power supply network or generator
Disconnect AC network before any wiring and connecting of the connector.
All
battery chargers can operate automatically and equally on single phase networks from 90 to 265VAC
and from 47 to 65Hz.
Generators
CRISTEC battery chargers are designed to operate from a generator.
Be careful: In some cases, the generators can produce high over voltages, in particular during start-up
phase. Before connecting the charger, please check its compatibility with the characteristics of the
generator: power, voltage, overvoltage, frequency, current, etc.
It's highly advised to disconnect the charger from the AC network during the generator starting phase.
Any damage to the charger due to a voltage surge will be excluded from the warranty.
The table below shows the maximum cross-section of the AC power supply cable admissible at the input of the connector:
12-40,12-60
WAGO WINSTA connector reference 770-103 allows the insertion of 2 cables made with 3 wires of 4mm² each.
4 DC outputs
Model
Circuit
breaker
maximum cross-section
2 x (3 x 4mm²)
Fuse
38