General Specifications
Typical Unit Components and Dimensions
W
S
D SCH
F
S
MODEL NUMBER
Series
PD = Friedrich Digital PTAC
System
X = Accessory
E = Cooling with or without electric heat
H = Heat Pump with Auxiliary Heat
Nominal Capacity
07 = 7,000 Btuh
12 = 12,000 Btuh
09 = 9,000 Btuh
15 = 15,000 Btuh
Voltage
K = 230/208V - 1 Ph. - 60 Hz.
R = 265V - 1 Ph. - 60 Hz.
Installation Checklist
q Inspect all components and accessories for damage before and after
installation.
q Remove the cardboard wall sleeve support and grill weatherboard.
q Check for proper wall sleeve installation in accordance with the wall
sleeve installation instructions.
q Check for a subbase kit or other means of structural support which
is required for ALL installations projecting more than 8" into room.
q Install the recommended Condensate Drain Kits for complete
condensate removal.
4
O
DOO
CH SS S
F O
CO
Nominal Heater Size (230V or 265V)
2 = 2.5 KW
* 5.0 kw only available on 9000, 12000 and 15000 BTU models
q Ensure that the chassis is installed in a 16" high x 42" wide wall sleeve
that is no deeper than 13 ¾". A baffle kit is required if the sleeve
exceeds that depth.
q Ensure that chassis and chassis front cover are installed and secured
properly.
q Ensure that drapes, bed, bedspread, furniture, etc. DO NOT block
either return or discharge air grilles.
q Inspect the condenser air inlet and outlet for any obstructions
(shrubbery, etc.)
q Ensure that 'reset' button is pressed on LCD device (only on cord
connected models).
PDXWS Wall Sleeve Dimensions:
16" H x 42" W x 13-¾" D
Front Cover Dimensions:
16" H x 42" W x 7-¾" D
Cut-Out Dimensions:
16-¼" x 42-¼"
G
Engineering Digit
Design Series
Note: All PTAC models with a C design series or
later come standard with Diamonblue seacoast
protection and digital controls.
Chassis
S = Standard
3 = 3.5 KW
5 = 5.0 KW*