Electrical Connection - Dimplex LA 35TUR+ Instructions D'installation Et D'utilisation

Pompe à chaleur air-eau réversible pour installation extérieure

Publicité

Les langues disponibles

Les langues disponibles

The following is true for heating-only operation of
the heat pump:
If the heat pump is used for heating purposes only, the hydraulic
connections at the liquefier can be connected the opposite way
round. In this case, the attached device label can be ignored.
Connection [A] is connected to the heating flow; connection [B] is
connected to the heating return.
Important:The notes/settings in the instructions of the heat
pump manager must always be observed and carried out accord-
ingly; not doing so will lead to malfunctions.
With this type of operation, cooling operation is not possible. The
system can only be operated in heating mode. The performance
ratings are valid as specified in the device information.
Minimum heating water flow
The minimum heating water flow rate through the heat pump
must be assured in all operating states of the heating system.
This can be accomplished, for example, by installing either a dual
differential pressureless manifold or an overflow valve. The pro-
cedure for setting an overflow valve is described in the chapter
"Start-up". When the minimum heating water flow rate is under-
shot, the plate heat exchanger in the refrigeration circuit can
freeze, which can lead to total loss of the heat pump.
The nominal flow rate is specified depending on the max. flow
temperature in the device information and must be taken into ac-
count during planning. With design temperatures below 30 C in
the flow, the design must be based on the max. volume flow with
5 K spread for A7/W35.
Antifreeze
A method of manual drainage (see illustration) should be pro-
vided for heat pumps which are exposed to frost. The antifreeze
function of the heat pump manager is active whenever the heat
pump manager and the heat circulating pump are ready for oper-
ation. The system has to be drained if the heat pump is taken out
of service or in the event of a power failure. The heating circuit
should be operated with a suitable antifreeze if heat pump sys-
tems are implemented in buildings where a power failure cannot
be detected (holiday home).
www.dimplex.de

7.3 Electrical connection

A standard four-core cable is used for connecting the heat pump
to the power supply.
The cable must be provided by the customer. The conductor
cross section is selected in accordance with the power consump-
tion of the heat pump (see appendix Device information) and the
applicable VDE (EN) and VNB regulations.
An all-pole disconnecting device with a contact gap of at least
3 mm (e.g. utility blocking contactor or power contactor) as well
as a 3-pole circuit breaker with common tripping for all external
conductors must be installed in the power supply (tripping current
in compliance with the device information).
The relevant components in the heat pump contain an internal
overload protection.
When connecting, ensure that the incoming supply has a clock-
wise rotating field.
Phase sequence: L1, L2, L3.
ATTENTION!
Ensure that there is a clockwise rotating field: With incorrect wiring the
starting of the heat pump is prevented. A corresponding warning is
indicated on the display of the heat pump manager (adjust wiring).
The control voltage is supplied via the heat pump manager.
The heat pump manager has a 230 V AC-50 Hz power supply
and is connected in compliance with its own operating instruc-
tions (16 A fuse).
ATTENTION!
The control cable is essential for the operation of air-to-water heat pumps
for outdoor installation. The control cable and mains cable are to be
routed separately. It is not permissible for the customer to extend the
control cable.
The control lines (not included in the scope of supply) have rec-
tangular plug connectors on both ends. One end is connected to
the heat pump manager, and the other end is connected to the
switch box in the heat pump. The plug connections to the heat
pump are located on the bottom of the switch box.
Two separate lines are used as control lines. One of the lines is
designed for the 230 V control voltage level, the other for the sig-
nal and/or extra-low voltage level.
More detailed information can be found in the operating instruc-
tions of the heat pump manager.
For detailed information, see circuit diagrams in the appendix.
452163.66.06 · FD 9506
LA 35TUR+
EN-7