Télécharger Imprimer la page

GE GFD48 Manuel D'utilisation Et Instructions D'installation page 19

Publicité

Les langues disponibles

Les langues disponibles

GAS REQUIREMENTS
WARNING
- Explosion Hazard
• Use a new CSA International approved flexible
gas supply line. Never reuse old flexible
connectors.
• Install an individual manual shut-off valve
within 6ft. of the dryer in accordance with the
National Fuel Gas Code, ANSI Z223.1/NFPA 54.
• Securely tighten all gas connections.
• If connected to LP gas, have a qualified person
make sure gas pressure DOES NOT exceed 13"
water column.
• Examples of a qualified person include: licensed
heating personnel, authorized gas company
personnel, and authorized service personnel.
• Failure to do so can result in death, explosion,
or fire.
• The installation must conform with local codes,
or in the absence of local codes, with the
National Fuel Gas Code, ANSI Z223.1/NFPA 54,
or the Natural Gas and Propane Installation
Code, CSA B149.1.
DRYER GAS SUPPLY CONNECTION
1
"
19 32
(4.05 cm)
"
3/8
NPT MALE THREAD GAS SUPPLY
4
" (11.27 cm)
7 16
NOTE: Add to vertical dimension
the distance between cabinet
bottom to floor.
You must use with this dryer a flexible metal
connector (listed connector ANSI Z21.24 / CSA 6.10).
The length of the connect shall not exceed 3 ft.
Installation Instructions
19
GAS SUPPLY
• A 1/8" National Pipe Taper thread plugged
tapping, accessible for test gauge connection,
must be installed immediately upstream of the
gas supply connection to the dryer. Contact
your local gas utility should you have questions
on the installation of the plugged tapping.
• Supply line is to be 1/2" rigid pipe and equipped
with an accessible shutoff within 6 feet of, and
in the same room with, the dryer.
• Use pipe thread compound appropriate for
natural or LP gas or use PTFE tape.
• Connect flexible metal connector to dryer and
gas supply.
WARNING
FOR USE WITH NATURAL GAS ONLY
Dryer as produced by manufacturer is to be used only
with a natural gas supply. A manufacturer-supplied
conversion kit is required to convert this dryer for
propane gas supply. Use propane gas conversion
kit WE25M87. Conversion must be made by properly
trained and qualified personnel in accordance with
local codes and ordinances.
ADJUSTING FOR ELEVATION
• Gas clothes dryers input ratings are based on
sea level operation and need not be adjusted
for operation at or below 2000 ft. elevation. For
operation at elevations above 2000 ft., input
ratings should be reduced at a rate of 4 percent
for each 1000 ft. above sea level.
• Installation must conform to local codes and
ordinances or, in their absence, the NATIONAL
FUEL GAS CODE, ANSI Z223.
- Fire Hazard

Publicité

loading