5.2
MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES
THE FRONT OF THE Appliance MUST BE FINISHED WITH ANY NON-COMBUSTIBLE MATERIALS
SUCH AS BRICK, MARBLE, GRANITE, ETC., AS LONG AS THE FINISHING MATERIAL DOES NOT GO
BELOW THE SPECIFIED DIMENSION AS ILLUSTRATED. AS AN ALTERNATIVE, YOU CAN FINISH THE
FACING AND / OR FINISHING MATERIAL MUST NEVER OVERHANG INTO THE Appliance OPENING.
THE Appliance REQUIRES A MINIMUM ENCLOSURE HEIGHT MEASURED FROM THE Appliance
IMPORTANT: The GD82 requires a minimum inside enclosure height of 72", measured from the bottom
of the appliance. For temperature requirements, this area must be left unobstructed.
72"
NON-
COMBUSTIBLE
* See "VENTING" section.
Appliance WITH DRYWALL, SEE DIAGRAM BELOW FOR DETAILS.
COMBUSTIBLE
8"
26"
12 1/4"
WARNING
!
RISK OF FIRE!
BASE.
COMBUSTIBLE NON-COMBUSTIBLE
BRICK
2"
INSULATION
SLEEVE
1"
0" IF NON-
COMBUSTIBLE
FINISHING IS
2"
USED SUCH AS
BRICK AND
STONE
2"
56"
MINIMUM
PLUS RISE*
29
W415-0748 / C / 08.20.12