Napoleon GD82NT-PA Instructions D'installation Et D'utilisation page 10

Publicité

10
3.2
TYPICAL VENT INSTALLATION
THE FIRST 2 FEET OF OUTER 7 " DIAMETER VENT PIPE FROM THE APPLIANCE MUST BE WRAPPED
IN THE 1" THICK INSULATION SLEEVE (SUPPLIED). MAKE SURE THE INSULATION IS PULLED DOWN
TIGHT TO THE APPLIANCE WHEN INSTALLED. THERE AFTER, A 2" CLEARANCE ALL AROUND THE
VENT PIPE FROM COMBUSTIBLE MATERIALS ON ALL HORIZONTAL VENT SECTIONS IS REQUIRED.
10" MINIMUM
46"
When venting, the horizontal run must be kept to a maximum of 20 feet. If a 20 foot horizontal run is required,
the appliance must have a minimum vertical rise immediately off the appliance of 57". When terminating verti-
cally, the vertical rise is a minimum 3 feet and a maximum 40 feet above the appliance.
W415-0748 / C / 08.20.12
24" MAXIMUM
56"
PLUS
RISE
WARNING
!
* FIRST TWO
FEET
REQUIRES
INSULATION
SLEEVE
46"
16" MINIMUM
3 FEET
MINIMUM
40 FEET
MAXIMUM
45.6