Table 9. Protection Characteristics
UPS AC suppression joule
rating
UPS AC suppression
response time
Overload protection
Table 10. Battery Characteristics
Battery type
Battery voltage / AH
Battery charge current
Battery float voltage
Recharge time
Backup time
Low voltage shutdown
voltage
Min voltage for cold start
Hot-swappable battery
Table 11. Environment
Humidity
Audible noise
Storage temperature
Operating temperature
Operating elevation
Table 12. Weights and Dimensions
Net Weight, lb. (kg)
H x W x D, in. (cm)
BC350RNC(AG-075F)
Line Mode: 110% - Enter fault after five minutes; 120% - enter fault immediately.
Battery Mode: 110% shutdown in five seconds; 120% shutdown immediately
BC350RNC(AG-075F)
Sealed, maintenance-free, lead acid batteries.
Qty (1) 12V / 2.8AH
2 min / full load
7 min / half load
BC350RNC(AG-075F)
0-95% RH @ 0-40 C (non-condensing)
<40 dBA (1 m from the front side)
BC350RNC(AG-075F)
4.6 lbs (2.1 kg)
2.2 x 10.0 x 7.0 (5.8 x 25.5 x 18.0)
Eaton Tripp Lite Series Cloud Connected UPS Systems User Guide 934859—Rev C
Product Specifications
BC600RNC(AG-0760)
190 (AC)
Instantaneous
BC600RNC(AG-0760)
Qty (1) 12V / 3.6AH
.5A
13.7 VDC
8 hours
1.2 min / full load
5 min / half load
9.8V all load levels
11V
No
BC600RNC(AG-0760)
-15 to +50 ℃
0 to +50 ℃
0-2000 meters
BC600RNC(AG-0760)
4.8 lbs (2.2 kg)
3.1 × 11.0 × 7.0 (8.0 ×28.0
BC850RNC(AG-0761)
BC850RNC(AG-0761)
Qty (1) 12V / 6AH
1.7 min / full load
8 min / half load
BC850RNC(AG-0761)
BC850RNC(AG-0761)
7 lbs (3.2 kg)
×18.0)
63