Product Specifications
C C h h a a p p t t e e r r 8 8 S S p p e e c c i i f f i i c c a a t t i i o o n n s s
8 8 . . 1 1
P P r r o o d d u u c c t t S S p p e e c c i i f f i i c c a a t t i i o o n n s s
Table 7. Input Characteristics
Capacity VA/Watts
Voltage AC
AC voltage range
AC amps
frequency
AC input protection
Line efficiency at full load
Table 8. Output Characteristics
Nominal output voltage
AC amps out
AC output voltage (Line
Mode)
AC output voltage (Battery
Mode)
Output AC waveform (Line
Mode)
Output AC waveform
(Battery Mode)
Frequency
Transfer time AC to DC
62
Eaton Tripp Lite Series Cloud Connected UPS Systems User Guide 934859—Rev C
BC350RNC(AG-075F)
350 / 210
High line set 145V +/- 5%
High line reset 140V +/- 5%
Low line reset 100V +/- 5%
3A
50 or 60 Hz +/- 3 Hz (default 60Hz)
(1) Thermal breaker 5A
>97.4%
BC350RNC(AG-075F)
2.9A (Nom); 3.7A (Max)
120V (follows input voltage 95–145VAC)
Simulated sine wave (Battery Mode)
50 or 60 Hz follows the AC input frequency
Battery cold start is 60Hz only
BC600RNC(AG-0760)
600/300
120 V
95–145VAC
Low line set 95V +/- 5%
5A
(1) Thermal breaker 7A
>97.91%
BC600RNC(AG-0760)
120V
5A (Nom) ; 6.3A (Max)
120V
Sine wave (AC Mode)
4 ~ 6 ms (Max < 10 ms)
BC850RNC(AG-0761)
850/450
7.1A
(1) Thermal breaker 10A
>97.20%
BC850RNC(AG-0761)
7.1A (Nom); 8.9A (Max)