Télécharger Imprimer la page

CEMO CUBE-Tank Informations Techniques page 29

Publicité

3.1
Handling using a crane
Danger!
Serious personal injury may occur if a
CUBE tank should fall.
It is prohibited to remain underneath the
suspended load while the crane is being
operated.
Check that the three clamps are screwed
firmly and correctly in place before each
time the crane is operated.
Important!
i
The cover must be closed and both seals
must be completely shut.
If unavailable
Fit three clamps with a minimum width of
170 mm and a diameter of 16 to 18 mm to the
side of the container.
Open out the three clamps fitted to the side of
the container.
Attach three suitable load-handling attachments
of equal length to the crane hangers.
The CUBE tank may be loaded/ unloaded on/
from the transport vehicle.
4. Installing the tank
When installing containers, please ensure good
stability. The container must stand so as to be level
and upright. The installation surface must be even
and have no edges or bumps. The container must
be cleaned thoroughly prior to installation. Contain-
ers must be positioned a sufÏcient distance from
walls, other structural elements and one another
to enable them to be checked visually for fill level,
leaks and condition at any time.
4.1
Installation outdoors
CUBE tanks are permitted for installation outdoors.
When installing outdoors, containers are to be
installed so as to avoid wind loads and keep the
impact of other weather-related effects (precipita-
tion, snow load, sunlight) to a minimum. Where the
containers are to be installed outdoors, the surface
should also be of road-quality construction and be
watertight. Section 3.1 (4) of the General Technical
Approval/General Design Certification Z-40.21-565
must also be observed in this regard.
4.2
Impact protection
CUBE tanks must be protected against dam-
age caused as a result of impacts by vehicles or
vandalism, e.g. by means of protected installation,
impact protection or by installing them in a suitable
area.
Section 3.1 (5) of the General Technical Approval/
General Design Certification Z-40.21-565 must
also be observed in this regard.
5. Filling and delivery systems
The filling and delivery line has already been fit-
ted on the CUBE tank by the manufacturer. The
relevant assembly and user manuals are included
with the accessory components such as counters,
fuel filters or hose reels.
All screw connections must be checked in all cases
to ensure they are leak-proof!
5.1
Ventilation line
CUBE Tanks intended for installation outdoors
feature a factory-fitted ventilation valve (2").
For CUBE Tanks that are installed inside buildings,
the ventilation valve on the tank must be removed
and the ventilation line laid by the customer so
that it leads to the open air. Section 3.2.3.2 of
the General Technical Approval/General Design
Certification Z-40.21-565 must also be observed in
this regard.
5.2
Overfill protection (limit indicator)
for diesel fuel
Versions for heating oil and diesel fuel include
factory-fitted overfill protection devices (limit indica-
tors) and the required installation depths have
been set.
GB