Electric Wiring
WARNING
Electrical wiring should be performed ONLY by a licensed electrician in compliance with local, state, and national electrical code NEC/ANSI/
NFPA 70, NFPA30, and NFPA 30A, as appropriate to the intended use of the pump. Threaded rigid conduit, sealed fittings, and conductor seal
should be used. The pump must be properly grounded. Improper installation or use of this pump can result in serious bodily injury, or death!
CAUTION
All pumps should be operated at the Rated Nameplate Voltage. Power should be supplied to the pump from a dedicated 20 amp circuit breaker.
No other equipment should be powered by this circuit. Wiring must be of sufficient size to carry the correct current for the pump. Voltage drop
will vary with distance to pump and size of wire; refer to the National Electrical Code (NEC), or local codes, for Voltage Drop Compensation to be
sure you are using the correct size wire for your application.
Wiring Procedure
WARNING
The "AUX." wire IS A LIVE WIRE when the switch is on! The "AUX" lead wire is insulated and enclosed when shipped. DO NOT connect this wire
without first verifying the "ON" line voltage of the wire for compatibility with the equipment to be installed. Maximum amperage on this wire is
1 amp. The "AUX" wire must be insulated and enclosed in the junction box if not used.
115 VOLT WIRE DIAGRAM AUX LEAD RATED 1.0 AMP
ORANGE
AUX
BLACK
AC
WHITE
NEU
MOTOR
GREEN
GRN
1.
Remove the junction box cover and straighten the wires to make sure the stripped wire ends are accessible outside the junction box.
2.
Connect the pump wires to the power supply lines according to the diagram. Be certain to properly insulate the connections with the appropriate wire nuts or other connectors.
Note that the ground wire MUST be connected.
3.
Tuck the wires back into the junction box, verify proper placement of gasket, align cover with junction box holes and reinstall screws. Torque each screw to 90 ± 9 in-lbs.
Use the Voltage Selector Switch on the end of the pump to select the input voltage for the pump. NOTE: The pump comes from the factory pre-set to 115V AC position.
NOTICE
Be certain the gasket for the cover is in place, and the screws draw the cover down tight over the junction box. There must be no gap between
the junction box and it's cover.
14
AWG
62
115V AC
(60Hz motor)
(18.9)
214
230V AC
(50Hz motor)
(65.2)
221
230V AC
(60Hz motor)
(67.4)
fillrite.com
FR700V SERIES FUEL TRANSFER PUMPS
230 VOLT WIRE DIAGRAM AUX LEAD RATED 1.0 AMP
ORANGE
AUX
BLACK
AC
BLACK WITH
WHITE STRIPE
AC
GREEN
GRN
MAX CABLE LENGTH IN FEET (METERS)
SOLID WIRE
12
10
8
99
158
250
--
(30.2)
(48.2)
(76.2)
340
542
859
--
(103.6)
(165.2)
(261.8)
351
560
887
--
(107.0)
(170.7)
(270.4)
MOTOR
6
4
14
12
61
96
--
(18.6)
(29.3)
209
331
--
(63.7)
(100.9)
216
342
--
(65.8)
(104.2)
INSTALLATION AND OPERATION MANUAL
OFF
Conduit opening
1/2" NPT
ON
STRANDED WIRE
10
8
6
4
154
245
389
620
(46.9)
(74.7)
(118.6)
(189.0)
529
844
--
--
(161.2)
(257.3)
546
871
--
--
(166.4)
(265.5)
6