7. Starting, operation
Manufacturer-specific:
Index
Object
(decimal)
Name
65
SP1 bzw. FH1 16 Bit unsigned R/W
66
RP1 bzw. FL1 16 Bit unsigned R/W
67
OU1
SP2
68
respectively
FH2
RP2
69
respectively
FL2
70
OU2
72
Unit
73
HIGH
74
LOW
75
DS1
WIKA Operating instructions/Betriebsanleitung/Mode d'emploi/Instrucciones de servicio
Format
Access Value range
8 Bit Enume-
R/W
ration
16 Bit unsigned R/W
16 Bit unsigned R/W
8 Bit Enume-
R/W
ration
8 Bit Enume-
R/W
ration
16 Bit unsigned R
16 Bit unsigned R
16 Bit unsigned R/W
1040 ... 9000
1000 ... 8960
0 = HNO = Hysteresis
Function, normally open
1 = HNC = Hysteresis
Function, normally closed
2 = FNO = Window Func-
tion, normally open
3 = FNC = Window Func-
tion, normally closed
1040 ... 9000
1000 ... 8960
0 = HNO = Hysteresis
Function, normally open
1 = HNC = Hysteresis
Function, normally closed
2 = FNO = Window Func-
tion, normally open
3 = FNC = Window Func-
tion, normally closed
0 = bar
1 = Mpa
2 = kPa
3 = PSI
4 = kg/cm²
0 ... 10000
0 ... 10000
0 ... 50,000 (0 ... 50 s)
Factory
Note
setting
Switch point/Window
9000
high switch output 1
Reset point/Window
8200
low switch ouput 1
Switch point switch
0
output 1
Switch point/Window
9000
high switch output 2
Reset point/Window
8200
low switch ouput 1
Switching Function
0
Switching Output 2
Switching over the
measuring units. After
order-
writing access the MBA
related
and MBE must be read
in again.
-
Maxvalue memory
-
Minvalue memory
Switch delay time
0
Switch point 1
PSD-30
GB
19