7. Starting, operation
4-digit LED display
1. LED (red)
2. LED (red)
Operating Modes
System start
Display Mode
Programming Mode
Parameter
Parameter
Description
SP1 / SP2
Hysteresis function: Switch point Switch output (1 or 2)
FH1 / FH2
Window function: Window high switch output (1 or 2)
RP1 / RP2
Hysteresis function: Reset point switch output (1 or 2)
FL1 / FL2
Window function: Window Low switch output (1 or 2)
EF
Enhanced Programming Functions
RES
Return the set parameter to the Factory Settings
DS1
Switch Delay Time, which must occur without interruption before any electrical signal change occurs
(SP1 or SP2)
DS2
DR1
Switch Delay Time, which must occur without interruption before any electrical signal change occurs
(RP1 or RP2)
DR2
OU1
Switching Function Switching Output (1 or 2)
OU2
HNO = Hysteresis Function, normally open
HNC = Hysteresis Function, normally closed
FNO = Window Function, normally open
FNC = Window Function, normally closed
UNIT
Changing Units
(If the pressure range is higher than the display range, no change of the unit is posssible
and the parameter UNIT is not shown)
WIKA Operating instructions/Betriebsanleitung/Mode d'emploi/Instrucciones de servicio
- Display system pressure
- Display Menu Item
- Display Parameter
- Status Switch Output 1
- Status Switch Output 2 (Optional)
- Display is fully activated for 2s
- When the pressure switch is powered up within the range of the
hysteresis, the output switch is set to „not active" by default
- normal operation, displays system pressure
- Setting Parameters
GB
PSD-30
13