Balluff FT 50 RLA Serie Instructions De Service Et De Montage page 70

Publicité

Les langues disponibles

Les langues disponibles

8.5.8
Scaling analogue output (set 20 mA point)
Command (Byte 3): decimal 72; hexadecimal 0x48
Parameter:
Data
Reply (Byte 3):
decimal 89; hexadecimal 0x59
Parameter:
no
The transmitted measured value becomes the 20 mA value of the analogue output.
Example telegram
(in the example, the sensor has the address 1)
Master telegram
Designation
1. Byte
Address
2. Byte
Length
3. Byte
Command
4. Byte
Data
5. Byte
6. Byte
Check sum
8.5.9
„Autom. zero" function (with Q
Command (Byte 3): decimal 90; hexadecimal 0x5A
Parameter:
no
Reply (Byte 3):
decimal 89; hexadecimal 0x59
Parameter:
no
The output characteristics (4 ... 20 mA) are simultaneously displaced with this function. When this function is acti-
vated and Q
= +U
, the current measured value is set as the output value of 4 mA. The incline of the characteristic
1
B
curve is maintained. The max. value of the characteristics is limited by the measuring range.
Example telegram
(in the example, the sensor has the address 1)
Master telegram
Designation
1. Byte
Address
2. Byte
Length
3. Byte
Command
4. Byte
Check sum
70
Decimal
Hex.:
129
81
6
06
72
48
63
3F
63
3F
79
4F
as control input)
1
Decimal
Hex.:
129
81
4
04
90
5A
95
5F
Parameter format
12 bit data item: data 1
Sensor's reply telegram
Designation
1. Byte
Address
2. Byte
Length
3. Byte
Reply
4. Byte
Check sum
Sensor's reply telegram
Designation
1. Byte
Address
2. Byte
Length
3. Byte
Reply
4. Byte
Check sum
FT 50 RLA Disctance sensor - GB - 068-13671 - 19.05.2016-12
Mounting and
operating instructions
Decimal
Hex.:
129
81
4
04
89
59
92
5C
Decimal
Hex.:
129
81
4
04
89
59
92
5C