8.5
Examples for master commands
INFORMATION
Most command protocols are displayed in the ProgSensor software (sensor simulation).
8.5.1
Set switching output Q
Command (Byte 3): decimal 49; hexadecimal 0x31
Parameter:
Switching point 1
Configuration
D0: 0 = N.O., 1 = N.C.
D1: 1 = pulse stretching, 0 = OFF
Switching point 2
Reply (Byte 3):
decimal 89; hexadecimal 0x59
Parameter:
no
Switching output Q
is defined (switching points 1+2, configuration)
1
Example telegram
(in this example the sensor has the address 1, switching output is defined as N.O. without pulse stretching, switching
point 1 = 2049, switching point 2 = 0)
Master telegram
Designation
1. Byte
Address
2. Byte
Length
3. Byte
Command
4. Byte
Switching point 1
5. Byte
6. Byte
Configuration
7. Byte
Switching point 2
8. Byte
9. Byte
Check sum
8.5.2
Set switching output Q
Command (Byte 3): decimal 50; hexadecimal 0x32
Parameter:
Switching point 1
Configuration
D0: 0 = N.O., 1 = N.C.
D1: 1 = pulse stretching, 0 = OFF
Switching point 2
Reply (Byte 3):
decimal 89; hexadecimal 0x59
Parameter:
no
Switching output Q
is defined (switching points 1+2, configuration).
2
66
1
Decimal
Hex.:
129
81
9
09
49
31
33
21
0
00
0
00
0
0
0
00
24
18
2
Parameter format:
12 bit data item: data 1
7 bit data byte
12 bit data item: data 1
Sensor's reply telegram
Designation
1. Byte
Address
2. Byte
Length
3. Byte
Reply
4. Byte
Check sum
Parameter format
12 bit data item: data 1
7 bit data byte
12 bit data item: data 1
FT 50 RLA Disctance sensor - GB - 068-13671 - 19.05.2016-12
Mounting and
operating instructions
Decimal
Hex.:
129
81
4
04
89
59
92
5C