Télécharger Imprimer la page

Mitsubishi Electric TRANE TPVFYP54AM141 Serie Manuel D'installation page 23

Publicité

Les langues disponibles

Les langues disponibles

-Power supply cords of appliances shall not be lighter than design 245 IEC 57, 227 IEC 57, 245 IEC 53 or 227 IEC 53.
-A switch with at least 3 mm contact separation in each pole shall be provided by the air conditioner installation.
Minimum wire thickness (mm
Total operating current of
the Indoor unit
Main cable
F0 = 16 A or less *2
1.5
F0 = 25 A or less *2
2.5
F0 = 32 A or less *2
4.0
Apply to IEC61000-3-3 about Max. Permissive System Impedance.
*1 The Ground-fault interrupter should support Inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum curent of the indoor units × 1.2
F2 = {V1 × (Quantity of Type1)/C} + {V1 × (Quantity of Type2)/C} + {V1 × (Quantity of Type3)/C} + {V1 × (Quantity of Others)/C}
Indoor unit
V1
V2
TPVFY
38
1.6
C : Multiple of tripping current at tripping time 0.01s
Please pick up "C" from the tripping characteristic of the breaker.
<Example of "F2" calculation>
*Condition TPVFY × 3, C = 8 (refer to right sample chart)
F2 = 38 × 3/8
= 14.25
16 A breaker (Tripping current = 8 × 16 A at 0.01s)
*3 Current sensitivity is calculated using the following formula.
G1 = (V2 × Quantity of Type1) + (V2 × Quantity of Type2) + (V2 × Quantity of Type3) + (V2 × Quantity of Others) + (V3 × Wire length [km])
G1
Current sensitivity
30 or less
30 mA 0.1 sec or less
100 or less
100 mA 0.1 sec or less
Caution:
Do not use anything other than the correct capacity breaker and fuse. Using fuse, wire or copper wire with too large capacity may cause a risk of malfunction
or fire.
9.2. Connecting remote controller, indoor
and outdoor transmission cables
Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)
The "S" on indoor unit TB5 is a shielding wire connection. For specifications
about the connecting cables, refer to the outdoor unit installation manual.
Install a remote controller following the manual supplied with the remote control-
ler.
Connect the "1" and "2" on indoor unit TB15 to a MA remote controller. (Non-
polarized 2-wire)
Connect the "M1" and "M2" on indoor unit TB5 to a M-NET remote controller.
(Non-polarized 2-wire)
Connect the remote controller's transmission cable within 10 m [32 ft] using a
0.75 mm
[AWG18] core cable. If the distance is more than 10 m [32 ft], use a
2
1.25 mm
2
[AWG16] junction cable.
[Fig. 9.2.1] (P.5) MA Remote controller
[Fig. 9.2.2] (P.5) M-NET Remote controller
A Terminal block for indoor transmission cable
B Terminal block for outdoor transmission cable
C Remote controller
DC 9 to 13 V between 1 and 2 (MA remote controller)
DC 24 to 30 V between M1 and M2 (M-NET remote controller)
[Fig. 9.2.3] (P.6) MA Remote controller
9.1. Power supply wiring
Power supply cords of appliances shall not be lighter than design 245 IEC 57, 227 IEC 57, 245 IEC 53 or 227 IEC 53.
A switch with at least 3 mm contact separation in each pole shall be provided by the Air conditioner installation.
[Fig. 9.1.1] (P.5)
A Ground-fault interrupter
B Local switch/Wiring breaker
)
C Indoor unit
2
Ground-fault interrupter *1
D Pull box
Branch
Ground
1.5
1.5
20 A current sensitivity *3
Total operating current of
2.5
the Indoor unit
2.5
30 A current sensitivity *3
Main cable
4.0
4.0
40 A current sensitivity *3
F0 = 16 A or less *
2
F0 = 25 A or less *
2
F0 = 32 A or less *
2
Apply to IEC61000-3-3 about Max. Permissive System Impedance.
*1 The Ground-fault interrupter should support Inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum curent of the indoor units × 1.2
F2 = {V1 × (Quantity of Type1)/C} + {V1 × (Quantity of Type2)/C} + {V1 × (Quantity of Type3)/C} + {V1 × (Quantity of Others)/C}
Indoor unit
PEFY-NMAU
C : Multiple of tripping current at tripping time 0.01s
Please pick up "C" from the tripping characteristic of the breaker.
<Example of "F2" calculation>
*Condition PEFY-NMAU × 3, C = 8 (refer to right sample chart)
F2 = 38 × 3/8
= 14.25
➞ 16 A breaker (Tripping current = 8 × 16 A at 0.01s)
12
Wire thickness
V3
1.5 mm
2
48
2.5 mm
2
56
4.0 mm
66
2
9.3. Connecting electrical connections
Please identify the model name of the operation manual attached on the terminal
box cover with that shown on the rating name plate.
1. Remove the screw (1pc) holding the cover to dismount the cover.
[Fig. 9.3.1] (P.6)
2. Open knockout holes
(Recommend to use a screwdriver or the like for this work.)
[Fig. 9.3.2] (P.6)
3. Fix power source wiring to terminal box by using buffer bushing for tensile
force. (PG connection or the like.) Connect transmission wiring to transmis-
sion terminal block through the knockout hole of terminal box using ordinary
bushing.
[Fig. 9.3.3] (P.6)
Local switch (A)
Capacity
Fuse
16
16
Minimum wire thickness (mm
)
2
Ground-fault interrupter *
25
25
Branch
Ground
32
32
1.5
1.5
1.5
20 A current sensitivity *
2.5
2.5
2.5
30 A current sensitivity *
4.0
4.0
4.0
40 A current sensitivity *
V1
V2
38
1.6
A Screw holding cover (1pc)
B Cover
C Terminal box
D Knockout hole
E Remove
F Use PG bushing to keep the weight of the cable and external force from being
applied to the power supply terminal connector. Use a cable tie to secure the
cable.
G Power source wiring
H Use ordinary bushing
I Transmission wiring
J Conduit
K Side frame
L Knockout hole (for power source wiring)
M Washer (round) (accessory)
CPEVS: PE insulated PVC jacket
CVV: PVC insulated PVC sheath
Breaker for wiring (A)
(Non-fuse breaker)
20
Local switch (A)
Breaker for wir
1
30
(Non-fuse bre
Capacity
Fuse
40
3
16
16
25
25
3
3
32
32
23
20
30
40
6000
600
60
10
1
0.1
0.01
1

Publicité

loading