9. Mount positions
9.1. Vertical installations
The air handler must be supported on the bottom only and set on
a solid floor with a return plenum below or field supplied supporting
frame or plenum. Securely attach the air handler to the floor or
supporting frame or plenum.
A single side return can be used for the TPVFYP008, TPVFYP012,
TPVFYP018 and TPVFYP024 only. Dual side returns must be used
on all other models to ensure proper air flow. If the side return is
used it is the responsibility of the installer to ensure the ducts
are properly sized and sealed to the cabinet. When cutting in to
the side of the cabinet, use the provided dimples to avoid damaging
any internal structure or wiring.
PLENUM
FILTER
nits, refer to the
supporting frame or plenum.
9.A. Vertical Installations:
A single side return can be used for the PVFY-12, PVFY-18
supported on the bottom only and set on a solid floor with a return
plenum below or field supplied supporting frame or plenum.
and PVFY-24 only. Dual side returns must be used on all other
Securely attach the air handler to the floor or supporting frame or
plenum.
responsibility of the installer to ensure the ducts are properly sized
ontal (Right and
The side return can be used for the PVFY-12, PVFY-18 & PVFY-
and sealed to the cabinet. When cutting in to the side of the cabinet,
24 only. If the side return is used it is the responsibility of the
. The units are
use the provided dimples to avoid damaging any internal structure
24" is required for
installer to ensure the ducts are properly sized and sealed to
Regardless of
or wiring.
the cabinet. When cutting in to the side of the cabinet, use the
ounted level to
provided dimples to avoid damaging any internal structure or
wiring.
n
24"
FILTER
DUAL SIDE RETURN
SEAL BOTTOM OF AIR HANDLER
ADD TWO FILTERS
PVFY_Install_EN_09-30_Current Images.indd 7
10
11
SINGLE SIDE RETURN (TPVFYP008, 12, 18 & 24)
SEAL BOTTOM OF AIR HANDLER ADD FILTER
The air handler must be
SIDE RETURN
Unit Mounted on Return Plenum
12
PLENUM
FILTER
6
MITSUBISHI ELECTRIC C
DATE
DIM.mm
DRAWN
SCALE
1:5
CHECKED
NTS
DESIGNED
13
9
A