TROUBLESHOOTING
TROUBLESHOOTING - PRIMARY PUMP
SYMPTOM
POSSIBLE CAUSE(S)
Pump is not plugged in.
Blown fuse.
Low line voltage
Pump won't
start or run.
Defective motor.
Defective float switch.
Impeller
Float obstructed
Pump starts
Backflow of water from piping
and stops too
Faulty float switch
often.
Defective float switch
Restricted discharge (obstacle or ice in
Pump won't
piping)
shut off.
Float obstructed
Restricted intake screen
Low line voltage
Something caught in impeller
Worn or defective parts or plugged
Pump operates
impeller
but delivers
little or no
Check valve installed without vent hole.
water.
Restricted intake screen
Check valve is installed either backward or
upside down
TROUBLESHOOTING - BACKUP PUMP
SYMPTOM
Pump won't run.
Motor hums but pump won't run.
Pump runs but pumps very little or no water.
HYD983 (06-08-20)
Check and see if pump is plugged into a proper outlet.
If blown, replace with fuse of proper size.
If voltage under recommended minimum, check size of wiring from main switch
on property. If OK, contact power company or hydro authority.
Replace pump.
Replace float switch.
If impeller won't turn, remove lower pump body and locate source of binding.
Remove obstruction.
Install or replace check-valve.
Replace float switch.
Replace float switch.
Remove pump and clean pump and piping.
Remove obstruction.
Remove the pump and clean the intake screen and the impeller.
If voltage under recommended minimum, check size of wiring from main switch
on property. If OK, contact power company or hydro authority.
Remove the pump and clean out the impeller.
Clean impeller if plugged; otherwise replace pump.
Drill a 1/16" - 1/8" (1.6mm-3.2mm) dia. hole between pump discharge & check valve
(1-2" above where the discharge pipe screws into the pump discharge and below
the waterline).
Remove the pump and clean out the intake screen.
Be sure check valve is installed correctly.
CORRECTIVE ACTION
Check all the wiring connections.
Check for a low or defective battery.
Check that the automatic switch is free to move up and down.
Press the circuit breaker reset button on the control panel.
Check for low or defective battery.
Make sure a check valve is installed and functioning between the primary pump
discharge and the Battery Backup wye.
Check for an obstruction in the discharge pipe.
The discharge pipe length and/or height exceeds the capacity of the pump.
Check for a low or defective battery.
The Positive (+) and negative (–) pump wires are reversed. Disconnect them and
reconnect correctly.
CORRECTIVE ACTION
13