2. Installation location
ZM200, 250
M200, 250
Fig. 2-3
Fig. 2-4
(mm)
A
Fig. 2-5
B
Fig. 2-6
2.3. Outline dimensions (Outdoor unit) (Fig. 2-3)
2.4. Ventilation and service space
2.4.1. Windy location installation
When installing the outdoor unit on a rooftop or other location unprotected from the
wind, situate the air outlet of the unit so that it is not directly exposed to strong winds.
Strong wind entering the air outlet may impede the normal airflow and a malfunction
may result.
The following shows three examples of precautions against strong winds.
1 Face the air outlet towards the nearest available wall about 50 cm away from the
wall. (Fig. 2-4)
2 Install an optional air protect guide if the unit is installed in a location where strong
winds from a typhoon, etc. may directly enter the air outlet. (Fig. 2-5)
A Air protect guide
3 Position the unit so that the air outlet blows perpendicularly to the seasonal wind
direction, if possible. (Fig. 2-6)
B Wind direction