TECHNICAL DATA
MODEL
TYPE
OUTPUT
MIN - MAX
(1)
DELIVERY
(1)
FUEL
OPERATION
NOZZLES
STANDARD APPLICATIONS
AMBIANT TEMPERATUR
COMBUSTION AIR TEMPERATURE
ELECTRICAL SUPPLY
ELECTRIC MOTORS
FAN MOTOR
(starting star/delta for RLS400)
PUMP MOTOR
IGNITION TRANSFORMER
PUMP
delivery at 16.5 bar (kg/h)
pressure range (bar)
fuel temperatur (°C max)
ELECTRICAL POWER CONSUMPTION
ELECTRICAL PROTECTION
CONFORMITY TO EEC DIRECTIVES
NOISE LEVELS
(3)
Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m a.s.l.
(1)
Pressure at test point 5)(A)p.12 with zero pressure in the combustion chamber and maximum burner output.
(2)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output.
(3)
ACCESSORIES
(optional)
OUTPUT POWER REGULATOR KIT:
rates between the low and high flame output position, thus ensuring stable operating conditions in terms of temperature or pressure. Two compo-
nents should be ordered: • Power regulator to install to the burner; • probe to install to the boiler.
PARAMETER TO BE CHECKED
Temperature
Pressure
• KIT AZL (display and operating unit)
• PRESSURE SWITCH KIT (for leak detection control)
• KIT SOFTWARE INTERFACE
• INVERTER KIT
• KIT O
2
GAS TRAIN ACCORDING TO REGULATION EN 676
Note.
The installer is responsible for the addition of any safety device not forseen in the present manual.
RLS 300/EV MX
RLS 300/EV MX O2
kW
600 ÷ 3650
kg/h
LIGHT OIL, viscosity at 20 °C: 6 mm2/s (1.5 °E - 6 cSt)
NATURAL GAS: G20 (methane) - G21 - G22 - G23 - G25
- Continuous / Intermittent (min. 1 stop in 24 hours)
- Progressive two-stage or modulating by kit (see accessoires)
numero
1
Boilers: water. steam. diathermic oil
°C
0 - 40
°C max 60
3N ~ 400 / 230V +/-10% 50 Hz
rpm
V
kW
A
15,8 - 9,1
V
kW
A
V1 - V2
I1 - I2
kW max
IP 54
73/23 - 2006/95 - 89/336 - 2004/108 - 2006/42
dBA
Under modulating operation, the burner automatically adapts to one of an infinite number of firing
Range
- 100...+ 500°C
0...2,5 bar
Output probe
0...16 bar
Code 3010355
Code 3010344
Code 3010388
Code 3010379
Code 3010378
: see page 26.
8
RLS 400/EV MX
2024 D
2220 D
800 ÷ 4300
50 ÷ 309
70 ÷ 365
2900
2900
230/400
400/680
4,5
7,5
16 - 9
230/400
1,5
6,4/3,7
230 V - 2 x 5 kV
1,9 A - 35 mA
560
7 - 40
140
7,5
11,5
80
85
PROBE
Type
Code
PT 100
3010110
3010213
4...20 mA
3010214
(Kit installed in series on burner RLS 300/EV MX O2)
(Kit installed in series on burner RLS 300/EV MX O2)
(Kit installed in series on burner RLS 300/EV MX O2)
RLS 500/EV MX
05681 X
1120 ÷ 5050
95 ÷ 425
2900
400/680
12
18 - 10,5
-
7 - 30
140
15
84,5
POWER REGULATOR
Type
Code
RWF40 BASIC
3010356
RWF40 HIGH
3010357