3.2
Wiring diagram, technical data for pulsers
Pulse transmitter type RV
Cable 3 m
Polarity choice free
Ri 47 Ohm
• ambient temperature
–10° C ... 70° C
• switching element
Reed contact
• switching voltage
max. 48 V DC/AC
• switching current
max. 50 mA (Ri 47 Ω)
• switching capacity
max. 2 W
• static current
nil
• pulse value
see type plate
Pulse transmitter type IN and INA
Pay attention to polarity when connecting the plug.
• ambient temperature
–10° C ... 70° C
• switching element
slot initiator acc. to DIN 19234
• switching voltage
5 – 15 V DC
• residual ripple
< 5 %
• switching current
> 3 mA (at 8 V, 1 kΩ)
• static current
< 1 mA (at 8 V, 1 kΩ)
• pulse value
see type plate
• connection
cable min. 2 x 0,35 mm2 and 4...6 mm external diameter, on plug supplied with product or use option
pn 80019 with cable mounted.
3.3

Ancillary units

Some ancillary units require a programmation for pulse values or frequency (see their service instructions).
Pulse values of the meters: see type plates.
The frequency is calculated with th following formula:
3.4
Function control
Put installation into operating points 4.1 ... 4.4.
Check functioning of ancillaries.
18
+/–
+/–
5.65078.4
max. flow rate in litres / hour
pulse value in litres 3600
Rollcrimping 0,2 - 0,5 mm
= frequency in Hz