Linear Input over Limits AI1
i.o.L. 1
If AI is a linear input, allows to the process to overpass the limits (parameters and ).
Disabled (Default)
diSab.
Enabled
Enab.
8
Offset Calibration AI1
o.cA. 1
AI Offset calibration. Value added/subtracted to the process value (ex: usually correcting the
ambient temperature value).
-
..+
[digit
9
Gain Calibration AI1
G.ca. 1
Value multiplied to the process value to calibrate the working point. Ex: to correct the range from
..
°C showing ..
-
. %...+
. %, Default: . .
10
Latch-On AI1
Ltc. 1
Automatic setting of limits for AI linear input
Disabled (Default)
diSab.
Standard
Stnrd
Virtual Zero Stored
v .0.sto.
Virtual Zero at start
v .0.t.on.
11
Conversion Filter AI1
c.FL. 1
ADC Filter: Number of sensor readings to calculate mean that defines process value. NB: When
readings increase, control loop speed slows down. ... . (Default: )
12
Conversion Frequency AI1
c.Fr. 1
Sampling frequency of digital / analogue converter for AI . Increasing the conversion speed will
slow down reading stability
(example: for fast transients, as the pressure, it is advisable to increase sampling frequency).
4.17 Hz (Min. conversion speed)
4.17.Hz
6.25 Hz
6.25Hz
8.33 Hz
8.33Hz
10.0 Hz
10.0Hz
12.5 Hz
12.5Hz
16.7 Hz (Default) Ideal for noises
16. 7Hz
filtering 50 / 60 Hz
19.6 Hz
19.6Hz
13
Lower Current Error 1
L.c.E. 1
If AI is a -
mA input, it determines the current value below the probe error E-
(Default)
2.0 MA
2.2 MA
2. 4 MA
14÷17
Reserved Parameters - Group A
Reserved parameters - Group A
20 - ATR224 - DRR224 - User manual
] (degrees.tenths for temperature sensors). Default .
p.
°C, set the parameter to - .
2.6 MA
2.8 MA
3.0 MA
33.2 Hz
33.2Hz
39.0 Hz
39.0Hz
50.0 Hz
50.0Hz
62.0 Hz
62.0Hz
123 Hz
123Hz
242 Hz
242Hz
470 Hz (Max. speed conversion)
470Hz
3.2 MA
3. 4 MA
3.6 MA
is signaled.
3.8 MA