Digital input
5.1.c
ATR224-12ABC
14
15 16
DI1
0V
+V
(PNP)
DRR224-12ABC
17
16
9
DI1
+V
0V
(PNP)
Digital output
5.1.d
ATR224-12ABC
12
15
DO1
0V
(PNP)
DRR224-12ABC
9 10
0V DO1
(PNP)
Relay output Q1 - Q2 (for ATR224-12ABC)
5.1.e
3
7
Q1
Q2
2A 230V
2A 230V
4
8
Resistive
Resistive
1/8 HP
1/8 HP
5
Relay output Q1 - Q2 (for DRR224-12ABC)
5.1.f
3
6
Q1
Q2
5A
5A
2
5
230V
230V
1
4
Life Curve
200
AC250V
DC30 V
100
AC125 V
AC125V COS ø=0.4
50
DC30 V t=7ms
20
10
AC250V COS ø=0.4
5
DC30 V t=15ms
0
2
3
4
1
Contact load current (A)
12 - ATR224 - DRR224 - User manual
Digital input can be enabled by parameters.
Close pin "DI1" on pin "+V" to enable digital input.
It is possible to put in parallel the digital inputs of different devices joining
together the pins (0V).
Digital output PNP (including SSR) for command or alarm.
Range 12 VDC/25 mA or 24 VDC/15mA selectable by parameter 282
Wire the positive control (+) of the solid state relay to the pin DO(x).
Wire the negative control (-) of the solid state relay to the pin 0V.
Capacity 2 A / 250 VAC for resistive loads.
See chart below.
Electrical endurance Q1 - Q2:
2 A, 250 VAC, resistive loads, 10
20/2 A, 250 VAC, cosφ = 0.3, 10
Capacity 5 A / 250 VAC for resistive loads.
See chart below.
Electrical endurance Q1 - Q2:
5 A, 250 VAC, resistive loads, 10
20/2 A, 250 VAC, cosφ = 0.3, 10
5
5
operations.
operations.
5
5
operations.
operations.
5
v.out.