Water Supply Connections Continued...
Air relief valve
Gas Supply
WARNING: Do not attempt to convert this water heater for use with a different type of gas other
than the type shown on the rating plate. Such conversion could result in hazardous operating conditions.
Please have a professional connect the gas pipe.
DO NOT use excessive force (over 31.5 ft lbs.) in tightening the pipe, particularly if pipe compound is
used, as the unit may be damaged.
Compound used on the threaded joints of the gas piping must be of the type resistant to the action of
LPG. Use compound sparingly and use on male threads only.
PLEASE NOTE: SH22 IS FOR OUTDOOR PERMANENT INSTALLATIONS ONLY AND SH22I IS FOR INDOOR PERMANENT INSTALLATIONS ONLY. THIS MANUAL
AND ALL ECCOTEMP CONTENT IS SUBJECT TO CHANGE WITHOUT NOTICE. PLEASE VISIT SUPPORT.ECCOTEMP.COM FOR MORE INFORMATION.
Support: Support.Eccotemp.com
Support: Support.Eccotemp.com
In regards to the HOT WATER OUTLET:
• Connections between the water heater and point(s) of use
should be as short and direct as possible.
• DO NOT use lead or non-approved plastic pipe.
Hot
• To conserve energy and minimize heat loss, insulation of hot
Water
Tap
water piping is recommended.
NOTICE: The flow rate of hot water may vary when more
than two faucets (appliances, fixtures, etc.) are being used
simultaneously.
Drain
NOTICE: The pipes MUST be completely drainable. If the hot
Valve
water faucets are located at a point higher than the water heater,
place a drain valve at the lowest point (see diagram to the left).
The supplied Manual Gas
Appliance Shutoff Valve
must be installed at the
gas connection of the
water heater at the time of
installation (see diagram to
the left).
The branch gas supply line
to the water heater should
be clean black steel pipe or
other approved gas piping
material. The minimum BTU
requirement for flex and/or
gas lines is 1" of black steel,
flex rated at 199K BTU.
A ground joint union or ANSI
design certified semi-rigid
or flexible gas appliance
connector should be installed
in the gas line close to the
water heater.
The National Fuel Gas Code
(NFGC) mandates a manual
gas shut off valve: See (NFGC)
for complete instructions.
Shop Online: www.Eccotemp.com
Shop Online: www.Eccotemp.com
A sediment trap should be installed at
the bottom of the gas line.
The inlet gas pressure to the water
heater must not exceed 10.5 in. w.c.
for natural or 13.5 in. w.c. for LPG.
For purposes of input adjustment,
the minimum inlet gas pressure (with
main burner on) is shown on the water
heater rating plate. If high or low gas
pressures are present, contact your gas
supplier for correction
The water heater and its indivdual
shutoff valve must be disconnected
from the gas supply piping system
during any pressure testing of that
system at test pressures in excess of
½ psi (3.5 kPa). The water heater must
be isolated from the gas supply piping
system by closing its individual manual
shutoff valve during any pressure
testing of the gas supply piping system
at test pressures equal to or less than
½ psi (3.5 kPa).
Phone: 866-356-1992
Store Locator: Eccotemp.com/locator
25