34
OEG CPA-E 100 series
4. Installation
4.3. Changing the position of the terminal box
The terminal box can be rotated by 45°.
Required steps:
1. Close the flow and return valves and release the pressure.
2. Loosen the four hexagon socket screws in the pump housing.
3. Turn the motor into the required position (see fig.)
4. Tighten the screws in CW direction.
5. Open the flow and return valves.
GB
High-efficiency wet-running circulation pump with screwed or flanged connection