Mounting and Installation
DE
US
FR
IT
ES
RU
NL
Separating "intrinsically safe circuits" from "non-intrinsically-safe circuits"
DK
SE
FI
PT
GR
PL
CZ
B
SK
HU
SL
RO
BG
Main contacts
LV
Auxiliary contacts 6/0.24
LT
EE
CH
KR
CN
20
SolConeX
Flange socket, 30 A
8571/25 series
Two conductors can be installed under one connection terminal.
The conductor material and conductor cross-section of both conductors must
be identical.
The conductors can be connected without any special prior measures.
• 6 mm/0.24 inch for a peak nominal voltage ≤ 375 V
• 8 mm/0.31 inch for a peak nominal voltage ≤ 750 V
• or with earthed shielding in accordance with UL 913 or UL 60079-11,
UL 60079-25 (sufficient current load capacity)
B [mm/inch]
12/0.47
• Open the enclosure.
• Strip the conductors.
• Insert the conductors into
the corresponding terminals
and clamp them
20631E00
(for the tightening torque,
see the "Technical data" chapter).
Insert the stripped conductor ends
completely under the terminal.
• Check if the conductors have
been clamped properly.
• Align the conductors. Make sure
that the clamping units are not
under tension.
• Close the enclosure
(for the tightening torque,
see the "Technical data" chapter).
294417 / 8571665300
2022-07-28·IO00·III·en·00