2.0 Framing and Clearances
2.1 Clearance to Sprinkler
•
In a situation where a sprinkler head is installed within the proximity to a #KZK discharge opening, the diagram below
MUST be followed.
•
The distance between a sprinkler head and discharge opening cannot be less than 60" (1524mm) in length at every
point from the origin of the discharge opening. You must also verify the sprinkler head sensor is set to the proper heat
setting so it does not activate when the room heats up from the fireplace being operated normally.
•
Please follow local building codes to determine what temperature setting is relevant for your installation.
Figure 2.1 - Clearance to Sprinkler
KZK-1510A
10
Rev. 10 — May 2023