Kozy Heat Fireplaces KZK-054 Manuel

Kit komfort zone pour utiliser avec le foyer au gaz à évacuation directe callaway-50 clw-50
Masquer les pouces Voir aussi pour KZK-054:

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

KOMFORT ZONE KIT
#KZK-054
For use with the Callaway-50 #CLW-50
Direct Vent Gas Fireplace
Starting Serial Number: 19 501780 50
English and French installation manuals are available through your
local dealer. Visit our website www.kozyheat.com.
Les manuels d'installation en français et en anglais sont disponibles
chez votre détaillant local. Visitez www.kozyheat.com .
1.0 INTRODUCTION .......................................................................3
1.1 Kit Contents.......................................................................................... 3
1.2 Suggested Configurations .............................................................. 4
1.3 Dimensions and Overview ............................................................. 5
1.4 Air Duct Run ......................................................................................... 6
2.0 FRAMING AND CLEARANCES ................................................7
2.1 Clearance to Sprinkler ...................................................................... 7
2.2 Framing.................................................................................................. 8
2.3 #KZK-054 Clearances ........................................................................ 9
3.0 FACING AND FINISHING .......................................................10
3.1 Non-combustible Requirements ................................................10
3.2 Combustible Finish ..........................................................................11
3.3 Hearth and Mantel Clearances ....................................................13
4.0 INSTALLATION .......................................................................14
Hussong Manufacturing Co., Inc.
P.O. Box 577, 204 Industrial Park Drive
Lakefield, MN 56150-0577, USA
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
HUSSONG MANUFACTURING CO., INC.
READ ALL THESE STEPS
BEFORE STARTING INSTALLATION.
LEAVE THESE INSTRUCTIONS WITH THE
APPLIANCE.
This kit must be installed by a qualified installer,
service agency, or gas supplier at the time of
the heater installation. These instructions must
be used in conjunction with the installation and
operation manual provided with the appliance.
Please read the appliance owner's manual
completely before performing any procedures in
these instructions.
This optional convection duct kit redistributes the
warm air flow away from the fireplace opening to
a more desirable location using natural convection
without the use of a fan. The warm air flow may be
relocated to a position higher up the wall, out the
sidewalls, or even to an adjacent room. The result
is much cooler wall temperatures above the fire-
place opening for locating televisions, artwork, etc.
Rev. 3, 5/20

Publicité

Chapitres

Table des Matières
loading

Sommaire des Matières pour Kozy Heat Fireplaces KZK-054

  • Page 1: Table Des Matières

    The result 2.1 Clearance to Sprinkler ..............7 2.2 Framing....................8 is much cooler wall temperatures above the fire- 2.3 #KZK-054 Clearances ................ 9 place opening for locating televisions, artwork, etc. 3.0 FACING AND FINISHING ............10 3.1 Non-combustible Requirements ..........10 3.2 Combustible Finish ................11...
  • Page 3: Introduction

    (4) take o collars included Figure 1.1, #KZK-054 #KZK-410-6 (4) - 10’ x 6” (aluminum ex) listed to UL-181Class 0 Air Duct Figure 1.2, #KZK-410-6 Komfort Zone Kit #KZK-054 R.3 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces INTRODUCTION 3...
  • Page 4: Suggested Configurations

    1.2 Suggested Configurations #KZK-054 front wall outlet #KZK-054 rear wall outlet #KZK-054 corner installation Figure 1.3, #KZK-054 Suggested Configurations 4 INTRODUCTION Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Komfort Zone Kit #KZK-054 R.3...
  • Page 5: Dimensions And Overview

    If you are mounting the plenum above the fireplace between 10’ (3m) to 20’ (6m) you will need (2) #KZK-410-6 kits and (1) #KZK-CPL6 coupler kit. Figure 1.5, #KZK-054 Overview Komfort Zone Kit #KZK-054 R.3 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces INTRODUCTION 5...
  • Page 6: Air Duct Run

    WHEN INSTALLING AIR DUCT PIPE MAINTAIN A MINIMUM 4" VERTICAL RISE FOR EVERY 12" HORIZONTAL RUN Minimum bend radius=5” (127mm) 4” (102mm) 12” (304mm) Figure 1.6, Minimum Vent Pipe Run 6 INTRODUCTION Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Komfort Zone Kit #KZK-054 R.3...
  • Page 7: Framing And Clearances

    Please follow local building codes to determine what temperature setting is relevant for your installation. 60” (1524mm) ½ ” Ceiling Sprinkler Head (63mm) Figure 2.1, KZK Clearance to Sprinkler Komfort Zone Kit #KZK-054 R.3 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces FRAMING AND CLEARANCES 7...
  • Page 8: Framing

    (1638mm) ½ ” (1130mm) 22” 76” (559mm) ½ ” (1930mm) (1638mm) ½ ” 22” (1130mm) (559mm) Figure 2.3,CLW-50 Unit Wall Enclosure Rough Opening 8 FRAMING AND CLEARANCES Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Komfort Zone Kit #KZK-054 R.3...
  • Page 9: Kzk-054 Clearances

    Figure 2.4, Minimum Clearance from Air Discharge to Ceiling ¾ ” (146mm) 5” (127mm) Steel Stud (required) STEEL FRAMING 22” (558mm) Figure 2.5, #KZK-054 and CLW-50 Framed Opening and Clearances Komfort Zone Kit #KZK-054 R.3 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces FRAMING AND CLEARANCES 9...
  • Page 10: Facing And Finishing

    No Screws Allowed No Screws Allowed ¾ 13” ¾ ” 13” ” (330mm) (95mm) (330mm) (95mm) Figure 3.2, Minimum Non-combustible Finishing Dimensions Screw Locations 10 FACING AND FINISHING Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Komfort Zone Kit #KZK-054 R.3...
  • Page 11: Combustible Finish

    NOTE: It is not required to use the #KZK-054 discharge trim (#KZK- Discharge trim is optional for this installation. 054DT) if desired to run finishing material up to the finishing material standoff.
  • Page 12 1” (25mm) thick Steel may be installed over Framing cement board Finishing Edge Fireplace Enclosure Floor Figure 3.6, #KZK-054 Combustible Wall Finish 12 FACING AND FINISHING Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Komfort Zone Kit #KZK-054 R.3...
  • Page 13: Hearth And Mantel Clearances

    Finishing Edge 6” (152mm) 9” (229mm) ¾ ” (248mm) 12” (305mm) Fireplace Enclosure Floor Figure 3.8, Hearth and Mantel Clearances for No Surround Komfort Zone Kit #KZK-054 R.3 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces FACING AND FINISHING 13...
  • Page 14: Installation

    24 inches. Install the #KZK-054DT discharge trim to the plenum after the wall finish is completed using (2) screws, if using the #KZK-054 plenum. Finishing material must not block and should run evenly along plenum opening. The #KZK-054DT discharge trim is optional depending on finishing material choice.
  • Page 16 KIT KOMFORT ZONE nº KZK-054 Pour utiliser avec le foyer au gaz à évacuation HUSSONG MANUFACTURING CO., INC. directe Callaway-50 nº CLW-50 Début du numéro de série : 19 501780 50 INSTALLATEUR : Laissez ce manuel avec l’appareil. PROPRIÉTAIRE : Conservez ce manuel pour le consulter.
  • Page 18: Introduction

    ⁄ ” (103mm) (4) collets de xation (fournis) Figure 1.1, Plénum, collets et garniture de sortie du kit no KZK-054 KZK-410-6 (4) - section de 10 pieds x 6 po conduit exible (aluminium) homolgué UL-181, Conduit d’air De Classe 0 Figure 1.2, Item no KZK-410-6...
  • Page 19: Configurations Suggérées

    1.2 Configurations suggérées KZK-054 sortie mural avant KZK-054 sortie mural arrière KZK-054 installations dans coin Figure 1.3, Configurations suggérées du KZK-054 4 INTRODUCTION Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Kit Komfort Zone nº KZK-054 R.3...
  • Page 20: Dimensions Et Vue D'ensemble

    Si vous installez le plénum à plus de 10 pieds (3 m) et moins de 20 pieds (6 m) au-dessus du foyer, vous aurez besoin de deux (2) kits nº KZK-410-6 et du kit de coupleurs nº KZK-CPL6. Figure 1.5, Vue d'ensemble du kit KZK-054 Kit Komfort Zone nº KZK-054 R.3 Hussong Mfg.
  • Page 21: Installation Des Conduit D'air

    À TOUS LES 12 PO (30 CM) DE COURSE HORIZONTALE Rayon de courbure minimal=5” (127mm) 4” (102mm) 12” (304mm) Figure 1.6, Installation de conduits d'air de longueur minimale 6 INTRODUCTION Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Kit Komfort Zone nº KZK-054 R.3...
  • Page 22: Encadrement Et Dégagements

    à votre installation. 60” (1524mm) ½ ” Tête de gicleur au plafond (63mm) Figure 2.1, Dégagement au gicleur du kit KZK Kit Komfort Zone nº KZK-054 R.3 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces ENCADREMENT ET DÉGAGEMENTS 7...
  • Page 23: Encadrement

    (1219mm) (1638mm) ½ ” (1130mm) 22” 76” (559mm) ½ ” (1930mm) (1638mm) ½ ” 22” (1130mm) (559mm) Figure 2.3, Encadrement et dégagement 8 ENCADREMENT ET DÉGAGEMENTS Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Kit Komfort Zone nº KZK-054 R.3...
  • Page 24: Dégagements D'encadrement

    Figure 2.4, Dégagement minimal de la sortie d'air au plafond ¾ ” (146mm) 5” (127mm) Acier d’encadrement requis ACIER D’ENCADREMENT 22” (558mm) Figure 2.5, Dégagements et dimensions minimum d'encadrement de plénum Kit Komfort Zone nº KZK-054 R.3 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces ENCADREMENT ET DÉGAGEMENTS 9...
  • Page 25: Façade Et Finition

    ¾ ” 13” ” (330mm) (95mm) (330mm) (95mm) Figure 3.2, Emplacements de vis permis (pour matériaux incombustibles de finition de dimensions minimales 10 FAÇADE ET FINITION Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Kit Komfort Zone nº KZK-054 R.3...
  • Page 26: Matériaux De Finition Combustibles

    KZK. La garniture de sortie d’air couvre complètement ces bords. NOTE: Il n’est pas obligatoire d’utiliser la garniture de sortie d’air du kit KZK-054, si vous désirez installer les matériaux de finition jusqu’aux espaceurs de dégagement des matériaux de finition. Les matériaux de Matériau finition ne doivent pas boucher l’ouverture de sortie d’air du plénum,...
  • Page 27 Bord de nition du foyer Plancher d’enceinte du foyer Figure 3.6, Matériaux de finition murale combustibles avec le KZK-054 12 FAÇADE ET FINITION Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Kit Komfort Zone nº KZK-054 R.3...
  • Page 28: Dégagements De L'âtre Et Du Manteau

    9” (229mm) ” (248mm) 12” (305mm) Plancher d’enceinte du foyer Figure 3.8, Dégagements de l’âtre et du manteau pour une installation sans contour Kit Komfort Zone nº KZK-054 R.3 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces FAÇADE ET FINITION 13...
  • Page 29: Installation

    Fixez le plénum à l’encadrement, avec des vis (ou clous) traversant la bride de fixation supérieure. 14 INSTALLATION Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Kit Komfort Zone nº KZK-054 R.3...
  • Page 30 Après avoir terminé l’installation des matériaux de finition murale, fixez au plénum la garniture de sortie d’air du KZK-054, en utilisant (2) vis si vous utilisez le plénum du kit KZK-054. Les matériaux de finition ne doivent pas boucher l’ouverture de sortie d’air du plénum, mais doivent border uniformément tout...

Ce manuel est également adapté pour:

19 501780 50

Table des Matières