I
NOTE
Should any programming problems or confusion occur, reset the Mem-
orized Default Settings by entering the program mode and setting P-17
to "rSt".
If recent programming changes were made but not saved, the reset will
return to the last saved defaults, which could differ from the factory
defaults.
P-1: Operating Mode
The following operating modes can be selected:
Automatic Mode by selecting "0"
Cool Only Mode by selecting "1"
Heat Only Mode by selecting "2"
P-2: High Fan Limit
The upper fan speed limit can be adjusted for various motors. The high fan limit is
adjusted with the system installed and operating. The values range from 65 through
95, arbitrary units.
➤ Use the Up and Down Buttons to select the desired speed.
– Increase the number for a higher fan speed.
– Decrease the number to lower the fan speed.
P-3: Low Fan Limit
The low fan limit determines the lowest output allowed for the low fan speed. The
values range from 30 through 64, arbitrary units.
➤ Use the Up and Down Buttons to select the low fan limit.
– Increase the number for a higher fan speed.
– Decrease the number to lower the fan speed.
I
NOTE
Once the high and low fan speed limits are set, the unit will automatically
readjust the remaining speeds to produce three equally spaced fan
speeds in both Automatic and Manual Fan Modes.
EN
Programming
19