NOTIFICATION LIST
WPM (CN) 234727, 239693
Message code Notifica-
tion from
30186
WPM
30188
WPM
30189
WPM
30190
WPM
30191
WPM
30192
WPM
30193
WPM
30196
WPM
30197
WPM
30198
WPM
30199
WPM
30201
WPM
30202
WPM
30203
WPM
30204
WPM
30205
WPM
30206
Heat pump
30207
WPM
30208
WPM
30209
WPM
30210
WPM
30211
WPM
30212
WPM
30213
WPM
30214
WPM
30215
WPM
30216
WPM
30217
WPE
30218
WPE
30219
WPE
30220
WPE
30221
WPE
WPMsystem
Reason for fault code being triggered
The heating circuit pump on the MFG cannot be
switched.
The 3-way diverter valve in the MFG cannot be
switched.
The emergency/booster heater in the MFG cannot
be switched.
Incorrect communication with the HP return tem-
perature sensor in the MFG.
Incorrect communication with the HP flow tempera-
ture sensor in the MFG.
Incorrect communication with the NHZ flow sensor
in the MFG.
Incorrect communication with the DHW tempera-
ture sensor in the MFG.
Incorrect communication with the heating circuit
flow rate sensor in the MFG.
Incorrect communication with the brine circuit flow
rate sensor in the MFG.
Incorrect communication with the heating circuit
pressure sensor in the MFG.
Incorrect communication with the brine pressure
sensor in the MFG.
Incorrect communication with the heating circuit
pump in the MFG.
Incorrect communication with the brine pump in
the MFG.
Incorrect communication with the 3-way diverter
valve in the MFG.
Incorrect communication with the emergency/
booster heater in the MFG.
Incorrect communication with the MFG.
Sensor value of "current sensor" outside the permis-
sible range
Sensor value of "outside temperature sensor" out-
side the permissible range
Sensor value of "buffer temperature sensor (heating
circuit sensor 1)" outside the permissible range
Sensor value of "flow temperature sensor" outside
the permissible range
Sensor value of "heating circuit sensor 2" outside
the permissible range
Sensor value of "heating circuit sensor 3" outside
the permissible range
Sensor value of "DHW cylinder sensor" outside the
permissible range
Sensor value of "source sensor" outside the permis-
sible range
Sensor value of "heat source 2" outside the permis-
sible range
Sensor value of "flow cooling sensor" outside the
permissible range
Sensor value of "DHW circulation temperature sen-
sor" outside the permissible range
Sensor value of "swimming pool sensor, primary"
outside the permissible range
Sensor value of "swimming pool sensor, secondary"
outside the permissible range
Sensor value of "heating circuit sensor 4" outside
the permissible range
Sensor value of "heating circuit sensor 5" outside
the permissible range
Sensor value of "DHW cylinder 2 sensor" outside the
permissible range
Possible cause of fault / remedy
Check the communication cable terminal or replace
the communication cable.
Check the communication cable terminal or replace
the communication cable.
Check the communication cable terminal or replace
the communication cable.
Check the communication cable terminal or replace
the communication cable.
Check the communication cable terminal or replace
the communication cable.
Check the communication cable terminal or replace
the communication cable.
Check the communication cable terminal or replace
the communication cable.
Check the communication cable terminal or replace
the communication cable.
Check the communication cable terminal or replace
the communication cable.
Check the communication cable terminal or replace
the communication cable.
Check the communication cable terminal or replace
the communication cable.
Check the communication cable terminal or replace
the communication cable.
Check the communication cable terminal or replace
the communication cable.
Check the communication cable terminal or replace
the communication cable.
Check the communication cable terminal or replace
the communication cable.
Check the communication cable terminal or replace
the communication cable.
Check sensor, leads and the relevant plug-in con-
nectors, and replace if faulty.
Check sensor, leads and the relevant plug-in con-
nectors, and replace if faulty. Terminal: WPM X 1.3
Check sensor, leads and the relevant plug-in con-
nectors, and replace if faulty. Terminal: WPM X 1.4
Check sensor, leads and the relevant plug-in con-
nectors, and replace if faulty. Terminal: WPM X 1.5
Check sensor, leads and the relevant plug-in con-
nectors, and replace if faulty. Terminal: WPM X 1.6
Check sensor, leads and the relevant plug-in con-
nectors, and replace if faulty. Terminal: WPM X 1.7
Check sensor, leads and the relevant plug-in con-
nectors, and replace if faulty. Terminal: WPM X 1.8
Check sensor, leads and the relevant plug-in con-
nectors, and replace if faulty. Terminal: WPM X 1.9
Check sensor, leads and the relevant plug-in con-
nectors, and replace if faulty. Terminal: WPM X 1.10
Check sensor, leads and the relevant plug-in con-
nectors, and replace if faulty. Terminal: WPM X 1.11
Check sensor, leads and the relevant plug-in con-
nectors, and replace if faulty. Terminal: WPM X 1.12
Check sensor, leads and the relevant plug-in con-
nectors, and replace if faulty. Terminal: WPE X3.4
Check sensor, leads and the relevant plug-in con-
nectors, and replace if faulty. Terminal: WPE X 3.5
Check sensor, leads and the relevant plug-in con-
nectors, and replace if faulty. Terminal: WPE X 3.6
Check sensor, leads and the relevant plug-in con-
nectors, and replace if faulty. Terminal: WPE X 3.7
Check sensor, leads and the relevant plug-in con-
nectors, and replace if faulty. Terminal: WPE X 3.8