Festo DADE-MVC Serie Mode D'emploi page 19

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Caution
Measuring fault.
Non-permitted load impedances can falsify the
measurement results and indicate incorrect positions.
• Observe at all costs the following load impedances
for faultless functioning:
– DADE-MVC-010: R ≥ 1 kΩ
– DADE-MVC-420: R ≤ 600 Ω (4...20 mA)
Connect the cable of the PLC to connection S1 ( 4 ).
Fasten the plugs with the aid of the union nut.
Pin
Colour
1
white
2
brown
3
green
4
yellow
5
grey
6
pink
7
blue
8
red
Festo DADE-MVC 1503b English
Assignment
+24 V power supply
Measured signal
(analogue)
Reference output
0 V measured signal
Reference input
Calibration input
Ready output
0 V power supply and
inputs/outputs
(0...10 V)
Connection S1
4
5
6
3
2
8
1
7
19