IFM ioControl CR2040 Manuel D'utilisation page 123

Table des Matières

Publicité

Index
S-idx
Designation
0x2021
0x00
Input – wire
break
0x01
Wire break
IN00IN07
0x2022
0x00
Output –
short circuit
0x01
Short circuit
OUT00...
OUT07
0x2023
0x00
Output –
open circuit
0x01
Open circuit
OUT00...
OUT07
0x2024
0x00
Output –
overload
0x01
Overload
OUT00...
OUT07
Data type
Default
ro
USINT
1
ro
USINT
0
ro
USINT
1
ro
USINT
0
ro
USINT
1
ro
USINT
0
ro
USINT
1
ro
USINT
0
Details
Largest sub-index supported
0 = normal
channels (bit coded)
1 = wire
0b---- ---X = IN00
break
0b---- --X- = IN01
0b---- -X-- = IN02
0b---- X--- = IN03
0b---X ---- = IN04
0b--X- ---- = IN05
0b-X-- ---- = IN06
0bX--- ---- = IN07
Largest sub-index supported
0 = normal
channels (bit coded)
1 = short
0b---- ---X = OUT00
circuit
0b---- --X- = OUT01
0b---- -X-- = OUT02
0b---- X--- = OUT03
0b---X ---- = OUT04
0b--X- ---- = OUT05
0b-X-- ---- = OUT06
0bX--- ---- = OUT07
Largest sub-index supported
0 = normal
channels (bit coded)
1 = open
0b---- ---X = OUT00
circuit
0b---- --X- = OUT01
0b---- -X-- = OUT02
0b---- X--- = OUT03
0b---X ---- = OUT04
0b--X- ---- = OUT05
0b-X-- ---- = OUT06
0bX--- ---- = OUT07
Largest sub-index supported
0 = normal
channels (bit coded)
1 = overload
0b---- ---X = OUT00
0b---- --X- = OUT01
0b---- -X-- = OUT02
0b---- X--- = OUT03
0b---X ---- = OUT04
0b--X- ---- = OUT05
0b-X-- ---- = OUT06
0bX--- ---- = OUT07
ioControl
UK
123