IFM ioControl CR2040 Manuel D'utilisation page 112

Table des Matières

Publicité

ioControl
Index
S-idx
Designation
0x1A03
0x00
Transmit
PDO map-
ping
Number of
mapped
objects in
PDO
0x01
PDO map-
ping
0x02
PDO map-
ping
0x1A04
0x00
Transmit
PDO map-
ping
Number of
mapped
objects in
PDO
0x01
PDO map-
ping
0x02
PDO map-
ping
0x1A05
0x00
Transmit
PDO map-
ping
Number of
mapped
objects in
PDO
0x01
PDO map-
ping
0x02
PDO map-
ping
0x03
PDO map-
ping
0x04
PDO map-
ping
112
Data type
Default
rw
USINT
0x02
rw
UDINT
0x2012 0120
rw
UDINT
0x2012 0220
rw
USINT
0x02
rw
UDINT
0x2012 0320
rw
UDINT
0x2012 0420
rw
USINT
0x04
rw
UDINT
0x2014 0110
rw
UDINT
0x2014 0210
rw
UDINT
0x2014 0310
rw
UDINT
0x2014 0410
Details
mapping transmit PDO 4 (periode
time IN00IN01)
number of integrated application
objects = 2
Index 0x2012, SubIndex 0x01
frequency input IN00: periode time of
the signal
Index 0x2012, SubIndex 0x02
frequency input IN01: periode time of
the signal
mapping transmit PDO 5 (periode
time IN02IN03)
number of integrated application
objects = 2
Index 0x2012, SubIndex 0x03
frequency input IN02: periode time of
the signal
Index 0x2012, SubIndex 0x04
frequency input IN03: periode time of
the signal
mapping transmit PDO 6 (duty cycle
of the signal on the frequency input
IN00, IN01, IN02, IN03)
number of integrated application
objects = 4
Index 0x2014, SubIndex 0x01
frequency input IN00: duty cycle of
the signal in ‰
Index 0x2014, SubIndex 0x02
frequency input IN01: duty cycle of
the signal in ‰
Index 0x2014, SubIndex 0x03
frequency input IN02: duty cycle of
the signal in ‰
Index 0x2014, SubIndex 0x04
frequency input IN03: duty cycle of
the signal in ‰

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Iocontrol cr2041Iocontrol cr2042

Table des Matières