Mounting hood Dimensions and Installation
Pendant (kPA-75, kPA-100)
Dimensions:
Installation:
1. Apply a corrosion-inhibiting grease, such as petroleum or soap-thickened mineral oils, in 3 lines, spaced approximately
120 degrees apart, perpendicular to the threads on the conduit stem.
2. Thread the pendant hood onto the 3/4 inch or 1 inch conduit stem.
3. Tighten the set screw inside the hood to a torque of 1.9 Nm min. 2.6 Nm max.
Appleton • 1.800.621.1506 • www.appletonelec.com
LUMINAIRE WITh SMALL hEAT SINk
LUMINAIRE WITh LARGE hEAT SINk
fIGURE 2: LUMINAIRE WITh PENDANT hOOD
Mounting Hoods
Pendant (KPA-75, KPA-100, KPAF-75, KPAF-100)
Mounting:
1. Apply tlc-3 grease in approximately three equal lines, spaced equally apart on the conduit ste
the 3/4 inch or 1 inch conduit stem.
2. tighten the set screw inside the hood.
JCT BOX
CONDUIT
STEM
SET SCREW
(INSIDE HOOD)
fIGURE 3: PENDANT hOOD DETAILS
Pendant Cone (KPCH-75, KPCH-100)
Mounting:
1. Apply tlc-3 grease in approximately three equal lines, spaced equally apart on the conduit ste
CEILING
PENDANT HOOD
DOC000084A000 Rev. 03 MY8382 • 03-AUG-22 • Page 6 of 46