4.6.3 Heating water demand –
Performance range 3
Heating of potable water 10 °C to 45 °C
Draw off capacity [litres/min.]
Heating of potable water 10 °C to 50 °C
Draw off capacity [litres/min.]
Heating of potable water 10 °C to 55 °C
Draw off capacity [litres/min.]
Heating of potable water 10 °C to 60 °C
Draw off capacity [litres/min.]
4.7 Return temperatures "Regudis W – HTF"
4.7.1 Return temperatures
Performance range 1 – 12 l/min
Potable water temperature
from
10 °C to
60 °C 19 °C
65 °C 18 °C 20 °C
70 °C 18 °C 19 °C
Flow
temperature [°C]
75 °C 17 °C 19 °C 20 °C 22 °C
80 °C 16 °C 18 °C 20 °C 22 °C
85 °C
4.7.2 Return temperatures
Performance range 2 – 15 l/min
Potable water temperature
from
10 °C to
60 °C 19 °C
65 °C 19 °C 19 °C
70 °C 18 °C 19 °C
Flow
temperature [°C]
75 °C 17 °C 18 °C 19 °C 21 °C
80 °C 16 °C 17 °C 19 °C 21 °C
85 °C
4.7.3 Return temperatures
Performance range 3 – 17 l/min
Potable water temperature
from
10 °C to
60 °C 16 °C
65 °C 15 °C 17 °C
70 °C 14 °C 16 °C
Flow
temperature [°C]
75 °C 14 °C 16 °C 17 °C 19 °C
80 °C 14 °C 15 °C 17 °C 18 °C
85 °C
45 °C 50 °C 55 °C 60 °C
20 °C 22 °C
45 °C 50 °C 55 °C 60 °C
19 °C 21 °C
45 °C 50 °C 55 °C 60 °C
16 °C 17 °C
23