ENGLISH
WARNING: To prevent elec tri cal shock, short cir cuit or arc ing, this
prod uct must be in stalled cor rect ly and water ingress must be avoid ed
before and during the in stal la tion.
WARNING: The purchaser should make the manufacturer aware of
any external effects or aggressive substances that the equipment may
be exposed to.
Before installing this product, read the installation instructions
completely.
CAUTION: Prolonged or repeated contact with the sealant in the core
sealer may cause skin irritation. Wash hands thoroughly. Overheating or
burning the sealant will produce fumes that may cause polymer fume
fever. Avoid contamination of cigarettes or tobacco. Consult MSDS VEN
0058 for further information.
Rated voltage
Ambient temperature
Ingress protection
Maximum pipe temperature:
Heater type
T
BTV
65°C
QTVR
110°C
XTV
121°C
KTV
150°C
HTV
205°C
VPL
See tables below
VPL: maximum pipe temperature in
dependence of heat type and voltage
Heater Type
230 Vac
5VPL2-CT
230°C
10VPL2-CT
210°C
15VPL2-CT
180°C
20VPL2-CT
150°C
Heater Type
385 Vac
5VPL4-CT
230°C
10VPL4-CT
215°C
15VPL4-CT
195°C
20VPL4-CT
150°C
Specific conditions for use using ATEX/UKEX or IECEx approvals:
For ambient temperatures >+40°C:
Use a power cable with continuous temperature resistance of minimum
+90°C
Use a metallic power cable gland approved for use in hazardous areas
(for example GL-38-M25-METAL).
For voltages >254 Vac and BTV, QTVR, XTV, KTV or HTV heating cables:
Use a power cable with continuous temperature resistance of minimum
+90°C
Use a metallic power cable gland approved for use in hazardous areas
(for example GL-38-M25-METAL).
|
6
nVent.com/RAYCHEM
nVent RAYCHEM JBM-100-E(P): 480 Vac**
JBM-100-L-E(P): 254 Vac
JBM-100-E(P): –55°C to +56°C**
JBM-100-L-E(P): –40°C to +40°C, except for VPL: in that case
ambient temperature can be up to +56°C.
IP66
continuous
max
254 Vac
277 Vac
225°C
225°C
200°C
195°C
145°C
105°C
Not allowed
400 Vac
480 Vac
230°C
230°C
215°C
205°C
195°C
160°C
150°C
150°C
T
intermittent
max
1000 h cumulative
85°C
110°C
250°C
250°C
260°C
VPL: Maximum pipe temperature
in dependence
≤ 150°C
30 A
30 A
30 A
30 A
≤ 150°C
30 A
30 A
30 A
30 A
T
power off
max
260°C
≤ 180°C
≤ 230°C
25 A
20 A
25 A
20 A
25 A
≤ 180°C
≤ 230°C
25 A
20 A
25 A
20 A
25 A