12. Specifications
Output signal (4 ... 20 mA version)
Analogue output
Load R
A
Factory configuration
Measuring range
Current values for error
signalling
Current value for
sensor short-circuit
Communication
Info data
Configuration and
calibration data
Configuration software
Voltage supply
Supply voltage U
Supply voltage input
Permissible residual
ripple of supply voltage
Time response
Switch-on delay,
electrical
Warm-up time
WIKA operating instructions model TR36
4 ... 20 mA, 2-wire
R
≤ (U
- 10 V) / 23 mA with R
A
B
The permissible load depends on the loop supply
voltage.
Measuring range 0 ... 150 °C [32 ... 302 °F]
Other measuring ranges are adjustable
Configurable in accordance with NAMUR NE 043
downscale < 3.6 mA (3.5 mA)
upscale > 21.0 mA (21.5 mA)
Not configurable in accordance with NAMUR NE 043
downscale ≤ 3.6 mA (3.5 mA)
Tag no., description and user message can be stored
in transmitter
Permanently stored
WIKAsoft-TT
→ Configuration software (multilingual) as a download
from www.wika.com
DC 10 ... 30 V
B
Protected against reverse polarity
10 % generated by U
current
Max. 4 s (time before the first measured value)
After approx. 4 minutes, the instrument will function to
the specifications (accuracy) given in the data sheet.
in Ω and U
A
< 3 % ripple of the output
B
in V
B