5. Commissioning, operation / 6. Configuration
Hysteresis on return to the measuring span
■
After the linear error limits have been exceeded, on return to the
measuring span, a hysteresis of 0.1 mA must be passed. This
hysteresis prevents the transmitter from jumping back and forth
between error signalling and measuring mode.
3.8 mA
Error
signalling
Error signalling
3.9 mA
Error limits and permissible measuring range
6. Configuration
Configuration is carried out using a USB interface with a PC via the
model PU-548 programming unit (accessories, order number: 14231581).
The connection with the thermometer is made via the appropriate adapter
cable (accessories: DIN connector, order number: 14005324).
Measuring range, dampening, error signalling, Tag no. and other
parameters can be adjusted (see configuration software).
WIKA operating instructions model TR36
4 mA
3.8 ...
4 ... 20 mA
4 mA
Measuring mode
Easy to use
■
LED status display
■
Compact design
■
No further voltage supply is needed for either
■
the programming unit or for the transmitter
(replaces programming unit model PU-448)
20 mA
20.5 mA
20 ... 20.5 mA
signalling
Error signalling
20.4 mA
EN
Error