7. Configuration
7. Configuration
Configuration is carried out via a USB interface with a PC via the
model PU-548 programming unit (accessories, order no. 14231581). The
EN
connection with the thermometer is made via the appropriate adapter
cable (Accessories: M12 x 1 circular connector, order no. 14003193).
Measuring range, damping, fault signal, TAG no. and other parameters
can be adjusted (see configuration software).
The measuring range is configurable between -50 ... +250 °C
(-58 ... +482 °F). The configuration software checks the required
measuring range and will only accept permissible values. Intermediate
values are configurable; the smallest increment is 0.1 °C or 0.1 °F. The
thermometers are delivered configured to customer specifications within
the configurable limits.
Please note:
The measuring range of the thermometer is limited by the application
range of the measuring element, not by the setting range of the
transmitter.
Maximum permissible temperatures:
At case with transmitter: 85 °C (185 °F)
■
Class A:
■
Without neck tube -30 ... +150 °C (-22 ... +302 °F)
With neck tube -30 ... +250 °C (-22 ... +482 °F)
Class B:
■
Without neck tube -50 ... +150 °C (-58 ... +302 °F)
With neck tube -50 ... +250 °C (-58 ... +482 °F)