2.7
VALEUR DU COUDE EN LONGUEUR D'ÉVENT
PIEDS POUCES
0,03
15°
0,45
30°
0,9
45°
1,35
90°*
2,7
* La première déviation de 90° a une valeur zéro et est illustrée dans la formule comme - 90°
2.8
ÉVACUATION SUR LE DESSUS TERMINAISON HORIZONTALE
Simple venting confi guration (only one 90° elbow)
For vent confi gurations requiring more than one 90° elbow, the following formulas apply:
Formula 1: H
< V
T
Formula 2: H
+ V
T
Example 1:
V
= 3 FT
1
V
= 8 FT
2
V
= V
+ V
= 3 FT + 8 FT = 11 FT
T
1
2
H
= 2.5 FT
1
H
= 2 FT
2
H
= H
+ H
= 2.5 + 2 = 4.5 FT
R
1
2
H
= .03 (three 90° elbows - 90°) = .03 (270° - 90°) = 5.4 FT
O
H
= H
+ H
= 4.5 + 5.4 = 9.9 FT
T
R
O
H
+ V
= 9.9 + 11 = 20.9 FT
T
T
Formula 1:
Formula 2:
Since both formulas are met, this vent confi guration is acceptable.
0,5
6,0
11,0
16,0
32,0
T
< 40 feet
T
H
< V
T
T
9.9 < 11
H
+ V
< 40 FT
T
T
20.9 < 40
(H
) < (V
)
T
T
See graph to determine the required vertical
rise V
40
39
30
REQUIRED
VERTICAL
20
RISE IN
FEET V
T
10
0
2.5
HORIZONTAL VENT RUN PLUS OFFSET IN
The shaded area within the lines represents
acceptable values for H
15.1
for the required horizontal run H
T
5
7.5
10
12.5
15
FEET H
T
and V
T
90°
V
2
90°
H
90°
1
V
1
16.1
15
.
T
17.5
20
T
H
2
W415-0785 / 11.10.09