Safety Manual
Connection diagram
Probability of dangerous Failure per Hour (PFH)
Probability of failure on demand (PFD) -
1 year proof test interval
Proof test interval (10% of loop PFD)
Safe Failure Fraction
Demand mode
Demand rate
Mean Time To Repair (MTTR)
Hardware Fault Tolerance (HFT)
Component Type
SIL capability
Description of the "Safe State"
1
Note
: The 9106 contains no lifetime limiting components, therefore the PFH
figures are valid for up to 12 years, according to IEC 61508.
2
Note
: The use of 9106 in SIL 3 applications requires that the connected PLC is
suitable for SIL 3 applications. see paragraph 4.6.
3
Note
: Depends on detection time in external controller. If detection time is xx
seconds, the Demand Rate shall be 100 times xx seconds.
4
Note
: Simple device (type A) where microprocessors and software have no
effect on safety output.
8. Hardware and software configuration.
All configurations of software and hardware versions are fixed from factory, and
cannot be changed by end-user or reseller.
This manual only covers products labelled with the product version (or range of
versions) specified on the front page.
9106 HART ® transparent repeater
Version No. V1R0
Ex input SIL 3
1.10E-08
Note
1
4.27E-05
2 years
98%
High
Note
3
24 hours
0
A, see Note
4
SIL 3, see Note
2
Output ≤ 3.6 mA or
Output ≥ 21 mA
6