Connecting The Video Fire Controller Fdv241 To The Fdnet (Without Connection To The Cctv System) - Siemens FDV241 Manuel De Mise En Service

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

All manuals and user guides at all-guides.com
9.4
Connecting the Video Fire Controller FDV241 to the FDnet
(without connection to the CCTV system)
Building Technologies
Fire Safety & Security Products
Fire panel
Manual call point
Fig. 7
Video Fire Controller connected to the FDnet, without connection to the
CCTV system
Fig. 8
Connections on the Video Fire Controller
Operate the device on the top-hat rail. See Section 8: Wall mounting.
1.
Connect a camera to the video input (1).
2.
If loop-through is necessary, set the terminating resistor (4) to Off and connect
the video cable extension to the video loop (3).
Connect an analogue monitor to the device (2).
3.
Connect the client PC to the device (6) using a patch cable.
4.
Connect the power supply cable to the device (8) first and then to the power
5.
source.
Switch on the analogue monitor.
6.
After a short wait, the IP address of the device will appear on the screen.
Connect the client PC to the power supply.
7.
Start the client PC.
8.
Set the IP address of the client PC. See Section 9.7: Setting the IP address of
9.
the client PC.
10. Install the software and configure it. See Section 10: Software and
Section 11: Configuration.
11. Disconnect the analog monitor and the client PC from the Video Fire
Controller.
12. Connect the Video Fire Controller to the FDnet (9).
Fire detectors
FDV241
FDnet
1 camera
Setup
23
11.2008

Publicité

Table des Matières
loading